LS-S02-120AMT-ZBZ/X

Safety position switch LS-ZBZ

Trade Price

£292.86

Per

1

Unit

EACH

Pack Quantity

1

LS-S02-120AMT-ZBZ/X
LS-S02-120AMT-ZBZ/X
LS-S02-120AMT-ZBZ/X
LS-S02-120AMT-ZBZ/X

Information

Eaton Moeller® series LS Position switch, 2 N/C, basic, magnet-powered interlock LS-S02-120AMT-ZBZ/X

Technical Specifications

Product Length/Depth

55 mm

Product Height

170 mm

Product Width

37 mm

Product Weight

0.417 kg

Certifications

CE

IEC/EN 60947

UL

CSA Class No.: 3211-03

UL Category Control No.: NKCR

CSA File No.: 012528

CSA

UL 508

UL File No.: E29184

CSA-C22.2 No. 14

IEC/EN 60947-5

Rated operational current for specified heat dissipation (In)

6 A

Repetition accuracy

0.02 mm (Contacts/switching capacity)

Terminal capacity (flexible with ferrule)

2 x (0.5 - 1.5) mm²

1 x (0.5 - 1.5) mm²

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

Rated operational current (Ie) at DC-13, 125 V

0.8 A

Diameter sensor

0 mm

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

Fitted with:

Interlock monitoring

Interface type

None

Force for positive opening - min

50 N

10.8 Connections for external conductors

Is the panel builder's responsibility.

Rated conditional short-circuit current (Iq)

1 kA

Actuator type

None

Sensor height

173 mm

Explosion safety category for gas

None

Sensor length

39 mm

Enclosure type

Cuboid

Ambient operating temperature - max

70 °C

Climatic proofing

Damp heat, cyclic, to IEC 60068-2-30

Damp heat, constant, to IEC 60068-2-78

Rated operational current (Ie) at AC-15, 24 V

6 A

Features

Forced opening

Expandable

Static heat dissipation, non-current-dependent Pvs

0 W

Voltage tolerance

0.85 x Us, Pick-up and drop-out values

1.1 x Us, Pick-up and drop-out values

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

Ambient operating temperature - min

-25 °C

Rated control supply voltage

120 V 50/60 Hz (Us, for magnet drive)

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

Mounting position

As required

Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V

6 A

Electric connection type

Cable entry metrical

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

Number of contacts (normally closed contacts)

2

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

Width sensor

60 mm

Heat dissipation per pole, current-dependent Pvid

0.13 W

Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V

4 A

Operating frequency

800 Operations/h

Product category

Basic units with spring-powered interlock (closed-circuit principle)

Action

2021118113756-Mechanical Limit Switches.xlsm-Data

Equipment heat dissipation, current-dependent Pvid

0 W

Heat dissipation capacity Pdiss

0 W

Suitable for

Safety functions

Terminal capacity (solid)

1 x (0.75 - 2.5) mm²

2 x (0.75 - 1.5) mm²

Power consumption

11 VA at 230 V AC (electromechanical actuation)

8 W at 24 V DC (electromechanical actuation)

8 VA at 120 V AC (electromechanical actuation)

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

Connection type

Screw terminal

Rated operational current (Ie) at DC-13, 220 V, 230 V

0.3 A

Switch function type

Slow-action switch

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

Overvoltage category

III

Degree of protection

IP65

NEMA Other

Enclosure material finishing

Other

Pollution degree

3

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

Rated impulse withstand voltage (Uimp)

4000 V AC

Actuator alignment

Other

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

Rated operational current (Ie) at AC-15, 125 V

6 A

Number of safety auxiliary contacts

2

Enclosure material

Insulated material

Plastic

Explosion safety category for dust

None

Duty factor

100 % (Magnet)

Type

Position switch

Safety position switch

10.2.2 Corrosion resistance

Meets the product standard's requirements.

Actuating force at beginning/end of stroke

25 N/15 N (plug-in/pull-out)

Supply frequency

Max. 400 Hz, Contacts

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.7 Inscriptions

Meets the product standard's requirements.

Number of contacts (normally open contacts)

0

Short-circuit protection rating

Max. 6 A gG/gL, Fuse, Contacts

Rated operational current (Ie) at DC-13, 110 V

0.8 A

Number of contacts (change-over contacts)

0

Lifespan

1,000,000 mechanical Operations

Shock resistance

10 g, Standard-action contact, Mechanical, Half-Sinusoidal shock 20 ms

Mechanical holding force

1200 N (according to GS-ET-19 (04/2004), XNW)

1700 N (according to GS-ET-19 (04/2004), XG, XW, XNG)

1600 N (according to GS-ET-19 (04/2004), XWA, XFG, XF)

Rated operational current (Ie) at DC-13, 24 V

3 A

Rated insulation voltage (Ui)

400 V