Trade Price
£292.86
Per
1
Unit
EACH
Pack Quantity
1
Eaton Moeller® series LS Position switch, 2 N/C, basic, magnet-powered interlock LS-S02-120AMT-ZBZ/X
Product Length/Depth
55 mm
Product Height
170 mm
Product Width
37 mm
Product Weight
0.417 kg
Certifications
CE
IEC/EN 60947
UL
CSA Class No.: 3211-03
UL Category Control No.: NKCR
CSA File No.: 012528
CSA
UL 508
UL File No.: E29184
CSA-C22.2 No. 14
IEC/EN 60947-5
Rated operational current for specified heat dissipation (In)
6 A
Repetition accuracy
0.02 mm (Contacts/switching capacity)
Terminal capacity (flexible with ferrule)
2 x (0.5 - 1.5) mm²
1 x (0.5 - 1.5) mm²
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Rated operational current (Ie) at DC-13, 125 V
0.8 A
Diameter sensor
0 mm
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
Fitted with:
Interlock monitoring
Interface type
None
Force for positive opening - min
50 N
10.8 Connections for external conductors
Is the panel builder's responsibility.
Rated conditional short-circuit current (Iq)
1 kA
Actuator type
None
Sensor height
173 mm
Explosion safety category for gas
None
Sensor length
39 mm
Enclosure type
Cuboid
Ambient operating temperature - max
70 °C
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Rated operational current (Ie) at AC-15, 24 V
6 A
Features
Forced opening
Expandable
Static heat dissipation, non-current-dependent Pvs
0 W
Voltage tolerance
0.85 x Us, Pick-up and drop-out values
1.1 x Us, Pick-up and drop-out values
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Ambient operating temperature - min
-25 °C
Rated control supply voltage
120 V 50/60 Hz (Us, for magnet drive)
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Mounting position
As required
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V
6 A
Electric connection type
Cable entry metrical
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Number of contacts (normally closed contacts)
2
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Width sensor
60 mm
Heat dissipation per pole, current-dependent Pvid
0.13 W
Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V
4 A
Operating frequency
800 Operations/h
Product category
Basic units with spring-powered interlock (closed-circuit principle)
Action
2021118113756-Mechanical Limit Switches.xlsm-Data
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Suitable for
Safety functions
Terminal capacity (solid)
1 x (0.75 - 2.5) mm²
2 x (0.75 - 1.5) mm²
Power consumption
11 VA at 230 V AC (electromechanical actuation)
8 W at 24 V DC (electromechanical actuation)
8 VA at 120 V AC (electromechanical actuation)
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
Connection type
Screw terminal
Rated operational current (Ie) at DC-13, 220 V, 230 V
0.3 A
Switch function type
Slow-action switch
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Overvoltage category
III
Degree of protection
IP65
NEMA Other
Enclosure material finishing
Other
Pollution degree
3
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
Rated impulse withstand voltage (Uimp)
4000 V AC
Actuator alignment
Other
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Rated operational current (Ie) at AC-15, 125 V
6 A
Number of safety auxiliary contacts
2
Enclosure material
Insulated material
Plastic
Explosion safety category for dust
None
Duty factor
100 % (Magnet)
Type
Position switch
Safety position switch
10.2.2 Corrosion resistance
Meets the product standard's requirements.
Actuating force at beginning/end of stroke
25 N/15 N (plug-in/pull-out)
Supply frequency
Max. 400 Hz, Contacts
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
Number of contacts (normally open contacts)
0
Short-circuit protection rating
Max. 6 A gG/gL, Fuse, Contacts
Rated operational current (Ie) at DC-13, 110 V
0.8 A
Number of contacts (change-over contacts)
0
Lifespan
1,000,000 mechanical Operations
Shock resistance
10 g, Standard-action contact, Mechanical, Half-Sinusoidal shock 20 ms
Mechanical holding force
1200 N (according to GS-ET-19 (04/2004), XNW)
1700 N (according to GS-ET-19 (04/2004), XG, XW, XNG)
1600 N (according to GS-ET-19 (04/2004), XWA, XFG, XF)
Rated operational current (Ie) at DC-13, 24 V
3 A
Rated insulation voltage (Ui)
400 V
Datasheet