Trade Price
£196.24
Per
1
Unit
EACH
Pack Quantity
1
Eaton Moeller series NZM - Molded Case Circuit Breaker. Undervoltage release, 110-130VAC, 4
Product Length/Depth
107 mm
Product Height
51 mm
Product Width
64 mm
Product Weight
0.263 kg
Compliances
CE Marked
UL/CSA
IEC
RoHS conform
Certifications
UL 489
IEC 60947
CE marking
UL (Category Control Number DIHS)
CSA (Class No. 1437-01)
UL listed
CSA-C22.2 No. 5-09
CSA (File No. 22086)
CSA certified
UL (File No. E140305)
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Rated control supply voltage (Us) at AC, 50 Hz - min
110 V
10.4 Clearances and creepage distances
Meets the product standard's requirements.
Minimum command time - min
10 ms
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
Pick-up power consumption at AC (undervoltage release)
3.6 VA
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
Rated control supply voltage (Us) at DC - min
0 V
Pick-up power consumption at DC (undervoltage release)
2.5 W
Rated control supply voltage (Us) at AC, 50 Hz - max
130 V
Frequency rating
50 to 60 Hz
10.8 Connections for external conductors
Is the panel builder's responsibility.
Minimum command time - max
15 ms
Special features
Non-delayed disconnection of NZM circuit-breaker or N switch-disconnector when the control voltage sinks below 35 – 70% US.
For use with emergency-stop devices in connection with an emergency-stop button.
When the under-voltage trip is switched off, accidental contact with the circuit breaker’s primary contacts is prevented when switched on.
Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.
Rated control supply voltage (Us) at DC - max
0 V
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Rated control supply voltage
110 - 130 V 50/60 Hz
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Used with
NZM4(-4), N(S)4(-4)
Electric connection type
Screw connection
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Number of contacts (normally closed contacts)
0
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Voltage type
AC
Drop-out voltage of undervoltage release AC/DC - min
0.35 x Us
Frame
NZM4
Reaction time
23 ms
Suitable for
Off-load switch
Voltage tolerance - min
.85
Rated control voltage (relay contacts)
130 V AC
110 V AC
Power consumption
3.6 VA (Sealing AC)
2.5 W (sealing DC)
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
Drop-out voltage of undervoltage release AC/DC - max
0.7 x Us
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
Connection type
With bolt connection
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Voltage tolerance - max
1.1
Undelayed short-circuit release - min
0 A
Rated control supply voltage (Us) at AC, 60 Hz - min
110 V
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
Terminal capacity (solid/flexible conductor)
18 - 14 AWG (2x) at shunt release
0.75 mm² - 2.5 mm² (1x) for undervoltage releases, off-delayed with ferrule
18 - 14 AWG (2x) for undervoltage releases, off-delayed
0.75 mm² - 2.5 mm² (2x) for undervoltage releases, off-delayed with ferrule
18 - 14 AWG (1x) for undervoltage releases, off-delayed
0.75 mm² - 2.5 mm² (1x) at shunt release with ferrule
0.75 mm² - 2.5 mm² (2x) at shunt release with ferrule
18 - 14 AWG (1x) at shunt release
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Type
Accessory
Undervoltage release
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
Rated control supply voltage (Us) at AC, 60 Hz - max
130 V
Number of contacts (normally open contacts)
0
Undelayed short-circuit release - max
0 A
Number of contacts (change-over contacts)
0
Datasheet