Eaton Moeller series NZM - Molded Case Circuit Breaker. Remote operator, 110-130VDC, for size 3
Product Length/Depth
170 mm
Product Height
140 mm
Product Width
140 mm
Product Weight
2.8 kg
Compliances
UL/CSA
IEC
RoHS conform
Certifications
UL489
IEC60947
UL (Category Control Number DIHS)
CSA (File No. 22086)
CE marking
CSA certified
CSA (Class No. 1437-01)
CSA-C22.2 No. 5-09
UL (File No. E140305)
UL listed
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Operating voltage - max
1.1 x Us
Frame
NZM3
Signal duration of remote operator at switch off - min
250 ms
Rated control supply voltage (Us) at AC, 50 Hz - min
0 V
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Voltage tolerance - min
.85
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
Rated control supply voltage (Us) at DC - min
110 V
Power consumption
250 W (24 - 30 V DC)
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
Rated control supply voltage (Us) at AC, 50 Hz - max
0 V
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.8 Connections for external conductors
Is the panel builder's responsibility.
Lifespan, mechanical
15000 operations
Closing delay
80 ms
Voltage rating
110 - 130 V DC
Switch drive type
Motor drive
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Special features
Cannot be combined with switch-disconnector PN...
M22-CK11(20/02) dual auxiliary switch cannot be combined with NZM3-XR… remote operator
Voltage tolerance - max
1.1
Rated control supply voltage (Us) at AC, 60 Hz - min
0 V
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
Terminal capacity (solid/flexible conductor)
0.75 mm² - 2.5 mm² with ferrule
18 - 14 AWG
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Rated control supply voltage (Us) at DC - max
130 V
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Number of poles
Three-pole/Four-pole
Type
Accessory
Remote operator, can be synchronized
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
Breaking time
1000 ms
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Rated control supply voltage (Us) at AC, 60 Hz - max
0 V
Signal duration of remote operator at switch on - min
30 ms
Used with
NZM3(-4)
N(S)3(-4)
Operating voltage - min
0.85 x Us
Number of operations per hour - max
60
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Voltage type
DC
Datasheet