Eaton Moeller series NZM - Molded Case Circuit Breaker. Remote operator, 48-60VDC, for size 2
Product Length/Depth
150 mm
Product Height
105 mm
Product Width
105 mm
Product Weight
1.728 kg
Compliances
UL/CSA
IEC
RoHS conform
Certifications
UL (File No. E140305)
IEC60947
CSA (Class No. 1437-01)
CE marking
UL listed
CSA certified
UL489
CSA-C22.2 No. 5-09
CSA (File No. 22086)
UL (Category Control Number DIHS)
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Operating voltage - max
1.1 x Us
Frame
NZM2
Signal duration of remote operator at switch off - min
150 ms
Rated control supply voltage (Us) at AC, 50 Hz - min
0 V
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Voltage tolerance - min
.85
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
Rated control supply voltage (Us) at DC - min
48 V
Power consumption
250 W (24 - 30 V DC)
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
Rated control supply voltage (Us) at AC, 50 Hz - max
0 V
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.8 Connections for external conductors
Is the panel builder's responsibility.
Lifespan, mechanical
20000 operations
Closing delay
60 ms
Voltage rating
48 - 60 V DC
Switch drive type
Motor drive
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Special features
Cannot be combined with switch-disconnector PN...
Do not install M22-CK11(20/02) dual auxiliary contacts in the center auxiliary contact slot in NZM2-XRD
Voltage tolerance - max
1.1
Rated control supply voltage (Us) at AC, 60 Hz - min
0 V
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
Terminal capacity (solid/flexible conductor)
0.75 mm² - 2.5 mm² with ferrule
18 - 14 AWG
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Rated control supply voltage (Us) at DC - max
60 V
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Number of poles
Three-pole/Four-pole
Type
Accessory
Remote operator, can be synchronized
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
Breaking time
300 ms
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Rated control supply voltage (Us) at AC, 60 Hz - max
0 V
Signal duration of remote operator at switch on - min
30 ms
Used with
NZM2(-4)
N(S)2(-4)
Operating voltage - min
0.85 x Us
Number of operations per hour - max
120
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Voltage type
AC
Datasheet