DILM12-XP1

Parallel link (2x) DILM7..15/MP

Trade Price

£9.10

Per

1

Unit

EACH

Pack Quantity

1

DILM12-XP1

Information

Eaton Moeller® series DILM Paralleling link, for DILM7-12/MP20

Technical Specifications

Product Length/Depth

34 mm

Product Height

30 mm

Product Width

32 mm

Product Weight

0.039 kg

Certifications

CSA File No.: 012528

IEC/EN 60947-4-1

UL Category Control No.: NLDX

CSA

CSA-C22.2 No. 14-05

CE

UL 508

UL File No.: E29096

CSA Class No.: 3211-03

UL

Accessory/spare part type

Connecting bridge

Product category

Accessories

Protection

Protected against accidental contact in accordance to VDE 0106 part 100

Ambient operating temperature - min

-25 °C

Ambient operating temperature - max

60 °C

Terminal capacity

1 - 16 mm², solid

1 x (0.5 - 25) mm², stranded

2 x (0.5 - 16) mm², flexible with ferrule

6 x 9 x 0.8 mm Number of segments x width x thickness, Flat conductor

2 x (0.5 - 16) mm², stranded

1 x (0.5 - 25) mm², flexible with ferrule

Screwdriver size

2, Terminal screw, Pozidriv screwdriver

Tightening torque

4 Nm, Screw terminal

Conventional thermal current ith of main contacts (1-pole, open)

50 A

Equipment heat dissipation, current-dependent Pvid

0.2 W

Heat dissipation capacity Pdiss

0 W

Rated operational current for specified heat dissipation (In)

50 A

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions

Meets the product standard's requirements.

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

10.8 Connections for external conductors

Is the panel builder's responsibility.

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Document Links

Datasheet