DILA-XHIC02

aux.contact module, 2-poles, front

Trade Price

£9.32

Per

1

Unit

EACH

Pack Quantity

1

DILA-XHIC02
DILA-XHIC02
DILA-XHIC02
DILA-XHIC02

Information

Eaton Moeller® series DILA Auxiliary contact module, 2 pole, Ith= 16 A, 2 NC, Front fixing, Spring-loaded terminals, DILA, DILM7 - DILM38

Technical Specifications

Product Length/Depth

55 mm

Product Height

38 mm

Product Width

36 mm

Product Weight

0.045 kg

Compliances

CE Marked

Certifications

EN 60947-4-1

IEC 60947-4-1

UL 508

CSA Std. C22.2 No. 14-05

CSA File No.: 012528

UL Category Control No.: NKCR

CSA-C22.2 No. 14-05

VDE 0660

CE

UL

UL File No.: E29184

CSA Class No.: 3211-03

IEC/EN 60947

CSA

IEC/EN 60947-4-1

Catalog Notes

This item can only be ordered until December 31, 2023 with a maximum delivery date of May 31, 2024.

Features

Interlocked opposing contacts within an auxiliary contact module (according to IEC 60947-5-1 Annex L)

Functions

For standard applications

Fitted with:

Interlocked opposing contacts

Switching elements according to EN 50005

Number of poles

Two-pole

Electric connection type

Spring clamp connection

Degree of protection

IP20

Shock resistance

7 g, N/O auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms

5 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms

Lifespan, electrical

1,300,000 Operations (at 230 V, AC-15, 3 A)

Lifespan, mechanical

10,000,000 Operations (AC operated)

10,000,000 Operations (DC operated)

Model

Top mounting

Mounting method

Front fastening

Operating frequency

9000 Operations/h

Overvoltage category

III

Pollution degree

3

Protection

Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)

Rated impulse withstand voltage (Uimp)

6000 V AC

Type

Front mounting auxiliary contact

Used with

DILMP

DILL

DILA

DILM

DILM(C)

Ambient operating temperature - min

-25 °C

Ambient operating temperature - max

60 °C

Ambient operating temperature (enclosed) - min

25 °C

Ambient operating temperature (enclosed) - max

40 °C

Ambient storage temperature - min

40 °C

Ambient storage temperature - max

80 °C

Climatic proofing

Damp heat, cyclic, to IEC 60068-2-30

Damp heat, constant, to IEC 60068-2-78

Terminal capacity (flexible with ferrule)

1 x (0.75 - 1.5) mm², Spring-loaded terminals

2 x (0.75 - 1.5) mm², Spring-loaded terminals

Terminal capacity (solid)

2 x (0.75 - 2.5) mm², Spring-loaded terminals

1 x (0.75 - 2.5) mm², Spring-loaded terminals

Terminal capacity (solid/stranded AWG)

18 - 14

Screw size

M3.5, Terminal screw

Screwdriver size

0.6 x 3.5 mm, Spring-loaded terminals

Conventional thermal current ith at 60°C (3-pole, open)

16 A

Rated operational current (Ie)

10 A at 24 V, DC L/R <= 15 ms (with 1 contact in series)

3 A at 110 V, DC L/R <= 15 ms (with 1 contact in series)

0.5 A at 110 V, DC L/R <= 50 ms (with 3 contacts in series)

10 A at 60 V, DC L/R <= 15 ms (with 2 contacts in series)

6 A at 110 V, DC L/R <= 15 ms (with 3 contacts in series)

1 A at 60 V, DC L/R <= 50 ms (with 3 contacts in series)

1 A at 220 V, DC L/R <= 15 ms (with 1 contact in series)

2.5 A at 24 V, DC L/R <= 50 ms (with 3 contacts in series)

0.25 A at 220 V, DC L/R <= 50 ms (with 3 contacts in series)

6 A at 60 V, DC L/R <= 15 ms (with 1 contact in series)

5 A at 220 V, DC L/R <= 15 ms (with 3 contacts in series)

Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V

4 A

Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V

4 A

Rated operational current (Ie) at AC-15, 500 V

1.5 A

Rated operational current (Ie) at DC-13, 60 V

1 A

Rated operational current (Ie) at DC-13, 110 V

0.5 A

Rated operational current (Ie) at DC-13, 220 V, 230 V

0.25 A

Rated insulation voltage (Ui)

690 V

Rated operational voltage (Ue) at AC - max

500 V

Short-circuit protection rating

Max. 10 A gG/gL, Fuse, Without welding, Auxiliary contacts

Short-circuit protection rating without welding

10 A gG/gL, 500 V, Max. Fuse, Contacts

Safe isolation

400 V AC, Between coil and auxiliary contacts, According to EN 61140

400 V AC, Between auxiliary contacts, According to EN 61140

Switching capacity (auxiliary contacts, general use)

10 A, 600 V AC, (UL/CSA)

1 A, 250 V DC, (UL/CSA)

Switching capacity (auxiliary contacts, pilot duty)

A600, AC operated (UL/CSA)

P300, DC operated (UL/CSA)

Connection type

Spring-loaded terminals

Code number

33 in combination with DILA(C)-31

24 in combination with DILA(C)-22

42E

Control circuit reliability

λ < 5 x 10-7 (1 failure at 2,000,000 operations for Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA)

Number of contacts (change-over contacts)

0

Number of contacts (normally closed contacts)

2

Number of contacts (normally open contacts)

0

Equipment heat dissipation, current-dependent Pvid

0 W

Heat dissipation capacity Pdiss

0 W

Heat dissipation per pole, current-dependent Pvid

0.16 W

Rated operational current for specified heat dissipation (In)

4 A

Static heat dissipation, non-current-dependent Pvs

0 W

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions

Meets the product standard's requirements.

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

10.8 Connections for external conductors

Is the panel builder's responsibility.

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Document Links

Datasheet