ZEB150-100-GF

Electronic overload 20-100A, Class 5-30

Trade Price

£381.01

Per

1

Unit

EACH

Pack Quantity

1

ZEB150-100-GF

Information

Eaton Moeller® series ZEB Overload relay, Direct mounting, Earth-fault protection: with, Ir= 20 - 100 A, 1 N/O, 1 N/C ZEB150-100-GF

Technical Specifications

Product Length/Depth

140.5 mm

Product Height

120 mm

Product Width

56 mm

Product Weight

0.74 kg

Certifications

UL Category Control No.: NKCR

UL File No.: E1230

UL 508

VDE 0660

CSA-C22.2 No. 14

CE

CSA Class No.: 3211-03

CSA

IEC/EN 60947

IEC/EN 60947-4-1

UL

CSA File No.: 2290956

Catalog Notes

Rated operational current: Switch-on and switch-off conditions based on DC-13, time constant as specified.

Earth fault protection

Trip at approx. > 0.5 x Ir in 2 s

Yes

Trip at approx. > 1.5 x Ir in 1 s

Features

Phase-failure sensitivity (according to IEC/EN 60947, VDE 0660 Part 102)

Functions

Filament bulb (24 V)

Class

Adjustable

Degree of protection

IP20

Mounting method

Direct attachment

Direct mounting

Overload release current setting - min

20 A

Overload release current setting - max

100 A

Overvoltage category

III

Pollution degree

3

Product Category

Electronic overload relays ZEB

Protection

Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)

Rated impulse withstand voltage (Uimp)

6000 V AC

6000 V (auxiliary circuits)

Shock resistance

Mechanical, According to IEC/EN 60068-2-27

15 g, Mechanical, According to IEC/EN 60068-2-27, Shock duration 10 ms

Suitable for

Branch circuits, (UL/CSA)

Voltage type

Self powered

Ambient operating temperature - min

-25 °C

Ambient operating temperature - max

65 °C

Ambient operating temperature (enclosed) - max

45 °C

Climatic proofing

Damp heat, constant, to IEC 60068-2-78

Damp heat, cyclic, to IEC 60068-2-30

Terminal capacity (flexible with ferrule)

2 x (0.75 - 2.5) mm², Control circuit cables

Terminal capacity (solid)

1 x (16 - 50) mm², Main cables

2 x (0.75 - 4) mm², Control circuit cables

Terminal capacity (solid/stranded AWG)

1 x (6 - 1), Main cables

2 x (18 - 12), Control circuit cables

Stripping length (main cable)

14 mm

Stripping length (control circuit cable)

8 mm

Screw size

M3.5, Terminal screw, Control circuit cables

Screwdriver size

1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver

2, Terminal screw, Control circuit cables, Pozidriv screwdriver

Tightening torque

7 lb-in, Screw terminals

0.8 - 1.2 Nm, Screw terminals, Control circuit cables

Conventional thermal current ith of auxiliary contacts (1-pole, open)

5 A

Rated control supply voltage (Us) at AC, 50 Hz - min

0 V

Rated control supply voltage (Us) at AC, 50 Hz - max

0 V

Rated control supply voltage (Us) at AC, 60 Hz - min

0 V

Rated control supply voltage (Us) at AC, 60 Hz - max

0 V

Rated control supply voltage (Us) at DC - min

0 V

Rated control supply voltage (Us) at DC - max

0 V

Rated frequency - min

50 Hz

Rated frequency - max

60 Hz

Rated operational current (Ie) at AC-15, 120 V

1.5 A

Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V

1.5 A

Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V

0.9 A

Rated operational current (Ie) at DC-13, 110 V

0.4 A

Rated operational current (Ie) at DC-13, 220 V, 230 V

0.2 A

Rated operational current (Ie) at DC-13, 24 V

0.9 A

Rated operational current (Ie) at DC-13, 60 V

0.75 A

Rated operational voltage (Ue) at AC - max

690 V

Short-circuit protection rating

Max. 6 A gG/gL, fuse, Without welding, Auxiliary and control circuits

Short-circuit current rating (high fault at 600 V)

100 kA, Fuse, SCCR (UL/CSA)

200 A, Class J, max. Fuse, SCCR (UL/CSA)

Switching capacity (auxiliary contacts, pilot duty)

R300, DC operated (UL/CSA)

B600, AC operated (UL/CSA)

Voltage rating - max

600 V

Number of auxiliary contacts (change-over contacts)

0

Number of auxiliary contacts (normally closed contacts)

1

Number of auxiliary contacts (normally open contacts)

1

Number of contacts (normally closed contacts)

1

Number of contacts (normally open contacts)

1

Equipment heat dissipation, current-dependent Pvid

25.4 W

Heat dissipation capacity Pdiss

0 W

Heat dissipation per pole, current-dependent Pvid

8.47 W

Rated operational current for specified heat dissipation (In)

100 A

Static heat dissipation, non-current-dependent Pvs

0 W

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions

Meets the product standard's requirements.

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

10.8 Connections for external conductors

Is the panel builder's responsibility.

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Electrical connection type of main circuit

Screw connection

Adjustable current range - min

20 A

Adjustable current range - max

100 A

Reset function

Push-button

Automatic

Document Links

Datasheet