EMT6-DB(230V)

Thermistor rly, hand/auto reset

Trade Price

£193.65

Per

1

Unit

EACH

Pack Quantity

1

EMT6-DB(230V)

Information

Eaton Moeller® series EMT6 Thermistor overload relay for machine protection, 230V50/60Hz, with lock

Technical Specifications

Product Length/Depth

103 mm

Product Height

83 mm

Product Width

23 mm

Product Weight

0.156 kg

Certifications

EN 55011

CSA File No.: 12528

CSA-C22.2 No. 14

IEC/EN 60947

UL File No.: E29184

CE

CSA Class No.: 3211-03

UL

UL Category Control No.: NKCR

IEC/EN 61000-4-3

UL 508

VDE 0660

IEC/EN 60947-8

IEC/EN 61000-4-2

CSA

Electric connection type

Screw connection

Functions

Manual or remote resetting

External reset possible

Test function via separate button

Notifications of mains and faults via LED display

Manual reset

Temperature measuring range - min

0 °C

Temperature measuring range - max

0 °C

Degree of protection

IP20

Mounting position

As required

Overvoltage category

III

Pollution degree

3

Product category

EMT6 thermistor overload relay for machine protection

Protection

Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)

Rated impulse withstand voltage (Uimp)

4000 V AC

6000 V AC

Safe isolation

250 V AC, Between the contacts, According to EN 61140

250 V AC, Between the contacts and power supply, According to EN 61140

Shock resistance

10 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms

Voltage type

AC

Ambient operating temperature - min

-25 °C

Ambient operating temperature - max

60 °C

Ambient operating temperature (enclosed) - min

25 °C

Ambient operating temperature (enclosed) - max

45 °C

Ambient storage temperature - min

45 °C

Ambient storage temperature - max

85 °C

Climatic proofing

Damp heat, cyclic, to IEC 60068-2-30

Damp heat, constant, to IEC 60068-2-78

Air discharge

8 kV

Burst impulse

2 kV, Supply cable

1 kV, Signal cable

According to IEC/EN 61000-4-4

Contact discharge

6 kV

Electromagnetic fields

3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)

10 V/m at 80 - 1000 MHz (according to IEC EN 61000-4-3)

1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)

Immunity to line-conducted interference

10 V (according to IEC/EN 61000-4-6)

Radio interference class

Class B (EN 55011)

Surge rating

According to IEC/EN 61000-4-5, power pulses (Surge), EMC

4 kV, asymmetrical, power pulses (Surge), EMC

2 kV, symmetrical, power pulses (Surge), EMC

Terminal capacity

20 - 14 AWG, solid or stranded

2 x (0.5 - 1.5) mm², flexible with ferrule

2 x (0.5 - 1.5) mm², solid

1 x (0.5 - 2.5) mm², flexible with ferrule

1 x (0.5 - 2.5) mm², solid

Screw size

M3.5, Terminal screw

Screwdriver size

1 x 6 mm, Terminal screw, Standard screwdriver

2, Terminal screw, Pozidriv screwdriver

Tightening torque

1.2 Nm, Screw terminals

Conventional thermal current ith of auxiliary contacts (1-pole, open)

6 A

Pick-up voltage

0.85 - 1.1 V x Uₑ

Power consumption

3.5 VA at AC

2 W at DC

Rated control supply voltage (Us) at AC, 50 Hz - min

230 V

Rated control supply voltage (Us) at AC, 50 Hz - max

230 V

Rated control supply voltage (Us) at AC, 60 Hz - min

230 V

Rated control supply voltage (Us) at AC, 60 Hz - max

230 V

Rated control supply voltage (Us) at DC - min

0 V

Rated control supply voltage (Us) at DC - max

0 V

Rated insulation voltage (Ui)

400 V

Rated operational current (Ie)

3 A at AC-14, 380 V 400 V 415 V (NC)

1 A at AC-15, 300 V (NO)

3 A at AC-15, 220 V 230 V 240 V (NO)

3 A at AC-14, 300 V (NO)

3 A at AC-15, 220 V 230 V 240 V

3 A at AC-14, 400 V (NC)

1 A at AC-15, 380 V 400 V 415 V (NC)

1 A at AC-15, 300 V (NC)

3 A at AC-14, 300 V (NC)

3 A at AC-15, 220 V 230 V 240 V (NC)

3 A at AC-14, 380 V 400 V 415 V (NO)

1 A at AC-15, 380 V 400 V 415 V (NO)

Rated operational voltage (Ue) - max

230 V

Reset resistance

1600 Ω

Short-circuit protection rating

Max. 6 A gG/gL, Fuse, Contacts

Trip resistance

3600 Ω

Voltage rating - max

600 V

Number of contacts (change-over contacts)

0

Number of contacts (normally closed contacts)

1

Number of contacts (normally open contacts)

1

Equipment heat dissipation, current-dependent Pvid

0 W

Heat dissipation capacity Pdiss

0 W

Heat dissipation per pole, current-dependent Pvid

0 W

Rated operational current for specified heat dissipation (In)

0 A

Static heat dissipation, non-current-dependent Pvs

1.5 W

Document Links

Datasheet