VHI20-PKZ0

Auxiliary contact for PKZ0

Trade Price

£13.95

Per

1

Unit

EACH

Pack Quantity

1

VHI20-PKZ0
VHI20-PKZ0
VHI20-PKZ0
VHI20-PKZ0

Information

Eaton Moeller® series PKZ0 Auxiliary contact, operates as an early-make contact, 2N/O early

Technical Specifications

Product Length/Depth

40 mm

Product Height

44 mm

Product Width

45 mm

Product Weight

0.029 kg

Certifications

CE

CSA

IEC/EN 60947-4-1

CSA Class No.: 3211-05

CSA File No.: 165628

UL 508

UL File No.: E36332

CSA-C22.2 No. 14

UL

UL Category Control No.: NLRV

Catalog Notes

For the premature voltage application of the U-release, e.g. in EMERGENCY STOP circuits according to EN 60204.

Electric connection type

Screw connection

Lifespan, electrical

100,000 Operations

Lifespan, mechanical

100,000 Operations

Model

Top mounting

Mounting method

Front fastening

Overvoltage category

III

Pollution degree

3

Product category

Accessories

Rated impulse withstand voltage (Uimp)

4000 V AC

Used with

Motor protective circuit-breaker

PKZ0-X(R)H(-M),MSC-… and PKZM0-X…M12

Ambient operating temperature - min

-25 °C

Ambient operating temperature - max

55 °C

Terminal capacity (solid/flexible with ferrule)

0.75 - 1.5 mm²

Terminal capacity (solid/stranded AWG)

18 - 16

Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V

1 A

Rated operational current (Ie) at DC-13, 24 V

2 A

Rated operational voltage (Ue) at AC - max

440 V

Rated operational voltage (Ue) at DC - max

250 V

Safe isolation

440 V, Between auxiliary contacts and main contacts, According to EN 61140

Short-circuit protection rating without welding

10 A gG/gL, Fuse, Auxiliary contacts

Connection type

Screw connection

Control circuit reliability

< 2 λ, < 1 failure at 100,000,000 Operations (at Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA)

Number of contacts (change-over contacts)

0

Number of contacts (normally closed contacts)

0

Number of contacts (normally open contacts)

2

Equipment heat dissipation, current-dependent Pvid

0 W

Heat dissipation capacity Pdiss

0 W

Heat dissipation per pole, current-dependent Pvid

0.03 W

Rated operational current for specified heat dissipation (In)

1 A

Static heat dissipation, non-current-dependent Pvs

0 W

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions

Meets the product standard's requirements.

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

10.8 Connections for external conductors

Is the panel builder's responsibility.

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Document Links

Datasheet