CL-PKZ0

Current limiter, 150kA @ 440V AC

Trade Price

£58.21

Per

1

Unit

EACH

Pack Quantity

1

CL-PKZ0
CL-PKZ0
CL-PKZ0
CL-PKZ0

Information

Eaton Moeller® series PKZ0 Current limiter, 3p, 63A, 400VAC/100kA, 690VAC/10kA

Technical Specifications

Product Length/Depth

56 mm

Product Height

90 mm

Product Width

45 mm

Product Weight

0.201 kg

Certifications

CSA Class No.: 3211-05

UL 508

CSA-C22.2 No. 14

IEC/EN 60947-4-1

CE

UL Category Control No.: NLRV

CSA

CSA File No.: 165628

UL

UL File No.: E36332

Functions

Short-circuit current limiter

Can be used for individual and group protection

Mounting Method

DIN rail

Mounting position

Next to or behind the motor protective circuit breaker

Overvoltage category

III

Pollution degree

3

Product category

Accessories

Rated impulse withstand voltage (Uimp)

6000 V AC

Type

Motor-protective circuit-breaker, non-auto-protected in order to increase switching capacity

Ambient operating temperature - min

-25 °C

Ambient operating temperature - max

55 °C

Rated uninterrupted current (Iu)

63 A

Rated conditional short-circuit current (Iq)

0 kA

Equipment heat dissipation, current-dependent Pvid

8.4 W

Heat dissipation capacity Pdiss

0 W

Heat dissipation per pole, current-dependent Pvid

2.8 W

Rated operational current for specified heat dissipation (In)

63 A

Static heat dissipation, non-current-dependent Pvs

0 W

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions

Meets the product standard's requirements.

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

10.8 Connections for external conductors

Is the panel builder's responsibility.

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Document Links

Datasheet