FAZ-K40/4

MCB, 40A, K-type, 4P, 15kA

Trade Price

£214.42

Per

1

Unit

EACH

Pack Quantity

1

FAZ-K40/4
FAZ-K40/4
FAZ-K40/4
FAZ-K40/4

Information

Eaton Moeller series xEffect - FAZ MCB. Miniature circuit breaker (MCB), 40 A, 4p, characteristic: K

Technical Specifications

Product Length/Depth

80 mm

Product Height

75.5 mm

Product Width

72 mm

Product Weight

0.467 kg

Compliances

RoHS conform

Certifications

IEC/EN 60898

IEC/EN 60947-2

EN45545-2

IEC 61373

Rated operational current for specified heat dissipation (In)

40 A

Rated short-circuit breaking capacity (EN 60898) at 230 V

0 kA

Mounting Method

Top-hat rail IEC/EN 60715

Current limiting class

3

Rated short-circuit breaking capacity (EN 60898) at 400 V

0 kA

Amperage Rating

40 A

Terminal capacity of screw terminals for main cable

10 mm² (2x)

Frequency rating - max

60 Hz

Rated short-circuit breaking capacity (IEC 60947-2) at 400 V

10 kA

Number of poles (total)

4

Terminal protection

Finger and hand touch safe, DGUV VS3, EN 50274

Rated short-circuit breaking capacity (IEC 60947-2) at 230 V

10 kA

Special features

Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity

Ambient operating temperature - max

75 °C

Heat dissipation per pole, current-dependent

0 W

Built-in depth

70.5 mm

Features

Additional equipment possible

Concurrently switching N-neutral

Lifespan, electrical

10000 operations

Connectable conductor cross section (solid-core) - min

1 mm²

Number of poles

Four-pole

Ambient operating temperature - min

-25 °C

Selectivity class

3

Terminal capacity (control cable)

25 mm² (1x)

Used with

Miniature circuit breaker

FAZ

Mounting position

As required

Equipment heat dissipation, current-dependent

12.1 W

Tripping characteristic

K

Frequency rating - min

50 Hz

Static heat dissipation, non-current-dependent

0 W

Application

Switchgear for industrial and advanced commercial applications

xEffect - Switchgear for industrial and advanced commercial applications

Voltage type

AC

Number of poles (protected)

4

Frame

45 mm

Terminals (top and bottom)

Twin-purpose terminals

Heat dissipation capacity

0 W

Release characteristic

K

Width in number of modular spacings

4

Busbar material thickness

0.8 mm - 2 mm

Power loss

12.1 W

Enclosure width

80 mm

Voltage rating

240 V AC / 415 V AC

Connectable conductor cross section (solid-core) - max

25 mm²

Degree of protection

IP40 (when fitted)

IP20

Overvoltage category

III

Pollution degree

2

Connectable conductor cross section (multi-wired) - min

1 mm²

Rated impulse withstand voltage (Uimp)

4 kV

Voltage rating at DC

60 V DC (per pole)

Admissible back-up fuse - max

125 A gL/gG

Rated switching capacity (IEC/EN 60947-2)

10 kA

Connectable conductor cross section (multi-wired) - max

25 mm²

Mounting width per pole

17.5 mm

Type

FAZ

Miniature circuit breaker

Operational switching capacity

7.5 kA

Direction of incoming supply

As required

Rated operational voltage (Ue) - max

400 V

Mounting width

17.5 mm

Rated insulation voltage (Ui)

440 V

Document Links

Datasheet