FAZ-K16/3

MCB, 16A, K-type, TP, 15kA

Trade Price

£119.67

Per

1

Unit

EACH

Pack Quantity

1

FAZ-K16/3
FAZ-K16/3
FAZ-K16/3
FAZ-K16/3

Information

Eaton Moeller series xEffect - FAZ MCB. Miniature circuit breaker (MCB), 16 A, 3p, characteristic: K

Technical Specifications

Product Length/Depth

80 mm

Product Height

75.5 mm

Product Width

54 mm

Product Weight

0.333 kg

Compliances

UL CSA09 (with supplementary protector only)

RoHS conform

Certifications

UL (File No. E177451)

UL 1077

CE marking

IEC/EN 60898

UL (Category Control Number QVNU2, QVNU8)

CSA-C22.2 No. 235

IEC/EN 60947-2

CSA (Class No. 3215-30)

CSA (File No. 204453)

North America (UL recognized, CSA certified)

EN45545-2

IEC 61373

Rated operational current for specified heat dissipation (In)

16 A

Rated short-circuit breaking capacity (EN 60898) at 230 V

0 kA

Mounting Method

Top-hat rail IEC/EN 60715

Current limiting class

3

Rated short-circuit breaking capacity (EN 60898) at 400 V

0 kA

Amperage Rating

16 A

Terminal capacity of screw terminals for main cable

10 mm² (2x)

Frequency rating - max

60 Hz

Rated short-circuit breaking capacity (IEC 60947-2) at 400 V

10 kA

Number of poles (total)

3

Terminal protection

Finger and hand touch safe, DGUV VS3, EN 50274

Rated short-circuit breaking capacity (IEC 60947-2) at 230 V

10 kA

Special features

Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity

Ambient operating temperature - max

75 °C

Heat dissipation per pole, current-dependent

0 W

Built-in depth

70.5 mm

Features

Additional equipment possible

Lifespan, electrical

10000 operations

Connectable conductor cross section (solid-core) - min

1 mm²

Number of poles

Three-pole

Ambient operating temperature - min

-25 °C

Selectivity class

3

Terminal capacity (control cable)

25 mm² (1x)

Used with

Miniature circuit breaker

FAZ

Mounting position

As required

Equipment heat dissipation, current-dependent

9 W

Tripping characteristic

K

Frequency rating - min

50 Hz

Static heat dissipation, non-current-dependent

0 W

Application

Branch circuits, not as BCPD

Switchgear for industrial and advanced commercial applications

xEffect - Switchgear for industrial and advanced commercial applications

Voltage type

AC

Number of poles (protected)

3

Frame

45 mm

Terminals (top and bottom)

Twin-purpose terminals

Heat dissipation capacity

0 W

Release characteristic

K

Width in number of modular spacings

3

Busbar material thickness

0.8 mm - 2 mm

Power loss

9 W

Enclosure width

80 mm

Voltage rating

240 V AC / 415 V AC

Connectable conductor cross section (solid-core) - max

25 mm²

Degree of protection

IP20

IP20 (IEC)

IP40 (when fitted)

UL/CSA Type: -

Overvoltage category

III

Pollution degree

2

Connectable conductor cross section (multi-wired) - min

1 mm²

Rated impulse withstand voltage (Uimp)

4 kV

Voltage rating at DC

60 V DC (per pole)

Admissible back-up fuse - max

125 A gL/gG

Rated switching capacity (IEC/EN 60947-2)

10 kA

Voltage rating (UL CSA 13)

480 Y/277 V AC

Connectable conductor cross section (multi-wired) - max

25 mm²

Mounting width per pole

17.5 mm

Type

FAZ

Miniature circuit breaker

Operational switching capacity

7.5 kA

Direction of incoming supply

As required

Rated operational voltage (Ue) - max

400 V

Mounting width

17.5 mm

Rated insulation voltage (Ui)

440 V

Document Links

Datasheet