EASY200-POW

PSU 115/230V..24/12V DC

Trade Price

£58.29

Per

1

Unit

EACH

Pack Quantity

1

EASY200-POW
EASY200-POW
EASY200-POW
EASY200-POW

Information

Eaton Moeller® series EASY Switched-mode power supply unit, 100-240VAC/24VDC/12VDC, 0.35A/0.02A, 1-phase, controlled

Technical Specifications

Product Length/Depth

58 mm

Product Height

90 mm

Product Width

36 mm

Product Weight

0.085 kg

Certifications

CE

UL Category Control No.: NRAQ

CSA-C22.2 No. 213-M1987

IEC 60068-2-27

UL File No.: E135462

EN 55022

CSA Class No.: 2252-01 + 2258-02

CSA File No.: 012528

CSA

UL

IEC 60068-2-6

EN 55011

IEC/EN 61000-4

CSA-C22.2 No. 142-M1987

UL 508

Features

Overload proof (by current limitation)

Proof against sustained short circuit, hickup mode (Output current 24 V DC)

Number of phases

1

Degree of Protection

IP20 (according to IEC/EN 60529, EN 50178, VBG 4)

Lamp load

2 W (cold, at 24 V DC)

LED indicator

Status Indication of 24 V DC output voltage: Continuous green light LED

Mounting Method

Screw fixing using fixing brackets ZB4-101-GF1 (accessories)

Top-hat rail fixing (according to IEC/EN 60715, 35 mm)

Power consumption

7 W typ.

Power loss

Normally 1 W

Product category

Control relays easyE4

Rated frequency - min

47 Hz

Rated frequency - max

63 Hz

Rated operational voltage

100/120/230/240 (-15 %/+10 %)

Used with

easyE4

Voltage type

DC

Constant acceleration

2 g, 57 - 150 Hz, according to IEC/EN 60068-2-6, Vibrations

Constant amplitude

0,15 mm, 10 - 57 Hz, according to IEC/EN 60068-2-6, Vibrations

Drop and topple

50 mm Drop height, Drop to IEC/EN 60068-2-31

Height of fall (IEC/EN 60068-2-32) - max

1 m

Mounting position

Vertical

Horizontal

Shock resistance

15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts

Air pressure

795 - 1080 hPa (operation)

Altitude

Max. 2000 m

Ambient operating temperature - max

55 °C

Ambient operating temperature - min

-25 °C

Ambient storage temperature - max

70 °C

Ambient storage temperature - min

40 °C

Environmental conditions

Clearance in air and creepage distances according to EN 50178

Condensation: prevent with appropriate measures

Relative humidity

5 - 95 % (non-condensing)

Air discharge

8 kV, according to IEC/EN 61000-4-2, Level 3, ESD

Burst impulse

2 kV, according to IEC/EN 61000-4-4, Level 3

Contact discharge

6 kV, according to IEC/EN 61000-4-2, Level 3, ESD

Electromagnetic fields

10 V/m (according to IEC EN 61000-4-3)

Immunity to line-conducted interference

10 V (according to IEC/EN 61000-4-6)

Radio interference class

Class B (EN 55022)

Class B (EN 55011)

Surge rating

6 kV, Surge voltage (EN 50178), 24 V, EMV

2 kV, Supply cables, symmetrical, power pulses (Surge), EMC

0.5kV, outgoer cables symmetrical, EASY…DC, IEC/EN 61000-4-5, level 2, 24 V EMC

Terminal capacity (flexible with ferrule)

0.2/2.5 mm²

Terminal capacity (flexible with ferrule AWG)

22 - 12

Terminal capacity (solid)

0.2/4 mm²

Terminal capacity (solid AWG)

22 - 12

Screwdriver size

3.5 x 0.8 mm, Terminal screw

Tightening torque

0.6 Nm, Screw terminals

Current limitation

20 mA, effectiveness of current limitation, 12 V DC (reference voltage), output current

0.4 A, effectiveness of current limitation, 24 V DC, output current

Insulation resistance

According to EN 50178

Potential isolation

SELV (VDE 0100 Part 410; IEC 60364-4-41, HD 384.4.41 S2) EN 60950, EN 50178 (primary/secondary)

Protection class

2 (IEC/EN 60536)

Input current at AC - max

0.17 A

Input voltage at AC 50 Hz - min

85 V

Input voltage at AC 50 Hz - max

264 V

Input voltage at DC - min

0 V

Input voltage at DC - max

0 V

Inrush current

5 A (at 25 °C, 230 V)

Mains failure bridging

> 10 ms (at 115 V, according to IEC/EN 61000-4-11)

> 20 ms (at 230 V, according to IEC/EN 61000-4-11)

Supply voltage

24 V DC, Output voltage

Efficiency

80 %

Output current at AC, 50 Hz - max

0.35 A

Output voltage

± 1 % (Effect with 25 - 100 % load change)

± 1 % (Effect of input voltage)

Output voltage at AC 50 Hz - max

12 V

Output voltage at DC - min

12 V

Output voltage at DC - max

24 V

Short-circuit protection

Yes, Proof against sustained short circuit, 12 V DC (reference voltage), Output current

Short-circuit protection rating

1.5 A slow, Fuse 115/230 V, Input voltage

Voltage tolerance

± 4 %, Rated output voltage 12 V DC

± 3 %, Rated output voltage 24 V DC

Equipment heat dissipation, current-dependent Pvid

0 W

Heat dissipation capacity Pdiss

0 W

Heat dissipation per pole, current-dependent Pvid

0 W

Rated operational current for specified heat dissipation (In)

0 A

Static heat dissipation, non-current-dependent Pvs

1 W

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions

Meets the product standard's requirements.

10.3 Degree of protection of assemblies

Meets the product standard's requirements.

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

10.8 Connections for external conductors

Is the panel builder's responsibility.

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

10.11 Short-circuit rating

Is the panel builder's responsibility.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility.

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Document Links

Datasheet