NZMN2-VE100-BT

NZM2 MCCB 3pole 100A 50kA

Trade Price

£650.05

Per

1

Unit

EACH

Pack Quantity

1

NZMN2-VE100-BT
NZMN2-VE100-BT
NZMN2-VE100-BT

Information

Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 100A, box terminals, selectivity protection

Technical Specifications

Product Length/Depth

149 mm

Product Height

184 mm

Product Width

105 mm

Product Weight

2.927 kg

Compliances

RoHS conform

Certifications

IEC/EN 60947

IEC

Voltage rating

690 V - 690 V

Rated impulse withstand voltage (Uimp) at auxiliary contacts

6000 V

Rated impulse withstand voltage (Uimp) at main contacts

8000 V

Rated short-time withstand current (t = 0.3 s)

1.9 kA

Rated short-time withstand current (t = 1 s)

1.9 kA

Amperage Rating

100 A

Instantaneous current setting (Ii) - min

1200 A

Instantaneous current setting (Ii) - max

1200 A

Overload current setting (Ir) - min

50 A

Overload current setting (Ir) - max

100 A

Short delay current setting (Isd) - min

100 A

Short delay current setting (Isd) - max

1000 A

Short-circuit release delayed setting - min

100 A

Short-circuit release delayed setting - max

1000 A

Short-circuit release non-delayed setting - min

1200 A

Short-circuit release non-delayed setting - max

1200 A

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz

85 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz

50 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz

35 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz

25 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz

5 kA

Rated short-circuit making capacity Icm at 240 V, 50/60 Hz

187 kA

Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz

105 kA

Rated short-circuit making capacity Icm at 440 V, 50/60 Hz

74 kA

Rated short-circuit making capacity Icm at 525 V, 50/60 Hz

53 kA

Rated short-circuit making capacity Icm at 690 V, 50/60 Hz

40 kA

Short-circuit total breaktime

< 10 ms

Electrical connection type of main circuit

Frame clamp

Isolation

300 V AC (between the auxiliary contacts)

500 V AC (between auxiliary contacts and main contacts)

Number of operations per hour - max

120

Handle type

Rocker lever

Utilization category

A (IEC/EN 60947-2)

Overvoltage category

III

Pollution degree

3

Lifespan, electrical

5000 operations at 690 V AC-3

6500 operations at 415 V AC-3

10000 operations at 415 V AC-1

6500 operations at 400 V AC-3

10000 operations at 400 V AC-1

7500 operations at 690 V AC-1

Direction of incoming supply

As required

Mounting Method

Built-in device fixed built-in technique

DIN rail (top hat rail) mounting optional

Fixed

Degree of protection

IP20 (basic degree of protection, in the operating controls area)

IP20

Degree of protection (IP), front side

IP66 (with door coupling rotary handle)

IP40 (with insulating surround)

Degree of protection (terminations)

IP10 (tunnel terminal)

IP00 (terminations, phase isolator and strip terminal)

Protection against direct contact

Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110

Shock resistance

20 g (half-sinusoidal shock 20 ms)

Number of auxiliary contacts (change-over contacts)

0

Number of auxiliary contacts (normally closed contacts)

0

Number of auxiliary contacts (normally open contacts)

0

Position of connection for main current circuit

Front side

Climatic proofing

Damp heat, constant, to IEC 60068-2-78

Damp heat, cyclic, to IEC 60068-2-30

Lifespan, mechanical

20000 operations

Document Links