Trade Price
£516.51
Per
1
Unit
EACH
Pack Quantity
1
Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3 p, 125A, box terminals
Product Length/Depth
149 mm
Product Height
184 mm
Product Width
105 mm
Product Weight
2.719 kg
Compliances
RoHS conform
Certifications
IEC
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Mounting Method
DIN rail (top hat rail) mounting optional
Built-in device fixed built-in technique
Fixed
Amperage Rating
125 A
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
Handle type
Rocker lever
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
Ambient storage temperature - min
40 °C
10.8 Connections for external conductors
Is the panel builder's responsibility.
Special features
Rated current = rated uninterrupted current: 125 A
Ambient operating temperature - max
70 °C
Position of connection for main current circuit
Front side
Features
Motor drive optional
Protection unit
Electrical connection type of main circuit
Frame clamp
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
36 kA
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Number of poles
Three-pole
Ambient operating temperature - min
-25 °C
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Instantaneous current setting (Ii) - min
750 A
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Instantaneous current setting (Ii) - max
1250 A
Overload current setting (Ir) - min
100 A
Short delay current setting (Isd) - min
0 A
Number of auxiliary contacts (normally closed contacts)
0
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
Overload current setting (Ir) - max
125 A
Voltage rating
690 V - 690 V
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Degree of protection
IP20
Overvoltage category
III
Short delay current setting (Isd) - max
0 A
Number of auxiliary contacts (change-over contacts)
0
Ambient storage temperature - max
70 °C
Release system
Thermomagnetic release
Pollution degree
3
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Functions
System and cable protection
Standard terminals
Box terminal
Type
Circuit breaker
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
Number of auxiliary contacts (normally open contacts)
0
Circuit breaker frame type
NZM2