Trade Price
£1,330.08
Per
1
Unit
EACH
Pack Quantity
Eaton Moeller series NZM - Molded Case Circuit Breaker. Earth-fault release, 0.1-3A, 4p
Product Length/Depth
132 mm
Product Height
103 mm
Product Width
140 mm
Product Weight
2.407 kg
Compliances
IEC
RoHS conform
Certifications
IEC/EN 60947-2
IEC/EN 60947-2 annex B
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Rated control supply voltage (Us) at AC, 50 Hz - min
280 V
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Mounting Method
Bottom
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
Rated fault current - max
3 A
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at AC, 50 Hz - max
690 V
Frequency rating
50 Hz
10.8 Connections for external conductors
Is the panel builder's responsibility.
Special features
Earth-fault release to IEC/EN 60947-2
Not UL/CSA approved
Suitable for use in three- and single-phase systems
Pulse-current sensitive according to core-balance principle
For 4 pole NZM2-4 circuit-breakers and N2-4 switch-disconnectors
Supply voltage-dependent Ue = 280 – 690 V 50 Hz
Sensitivity type
Pulse-current sensitive as per core-balance principle (type A)
Ambient operating temperature - max
70 °C
Power on-delay time - max
100 ms
Features
Sealable, setting buttons
Rated control supply voltage (Us) at DC - max
0 V
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Number of poles
Four-pole
Ambient operating temperature - min
-25 °C
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Used with
N2-4
NZM2-4
Four-pole
Mounting position
Vertical and 90° in all directions
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Application
In three- and single-phase systems
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Frame
96 mm
NZM2
Power on-delay time - min
100 ms
Current rating - min
15 A
Fault current detection range
50 Hz
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
Lifespan, mechanical
≧ 2000 operations
Voltage rating
280 - 690 V AC (independent of mains voltage)
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Degree of protection
IP20 (operating component area)
Rated control supply voltage (Us) at AC, 60 Hz - min
0 V
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
Terminal capacity (solid/flexible conductor)
As NZM2 standard terminal without ferrules
As NZM2 standard connection with ferrules
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Functions
Delay adjustable
Type
Accessory
Earth-fault releases
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
Rated control supply voltage (Us) at AC, 60 Hz - max
0 V
Current rating - max
250 A
Rated operating voltage (Ue) - max
690 V
Rated fault current - min
0.1 A
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Datasheet