Trade Price
£79.31
Per
1
Unit
EACH
Pack Quantity
Eaton Moeller series NZM - Molded Case Circuit Breaker. Internal communication module, RS485, Modbus RTU, suitable for NZM
Product Length/Depth
76 mm
Product Height
65 mm
Product Width
68 mm
Product Weight
0.008 kg
Compliances
UL/CSA
IEC
RoHS conform
Interface type (fieldbus)
Modbus RTU / RS485
Terminal capacity (stranded cable)
AWG 24 - AWG 20 (1x) at supply connection
0.25 mm² - 0.5 mm² (1x) at supply connection (uninsulated ferrule according to DIN46224 / 1)
0.2 mm² - 0.5 mm² (1x) at supply connection
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Frame
NZM2/3/4
Accessory/spare part type
Communication and measuring function
Communications module
Accessory
Stop bit
1, 2 (default 1)
Terminal capacity (solid cable)
0.2 mm² - 0.5 mm² (1x) at supply connection
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Strip length
6 mm (supply connection)
Participant type
Slave
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.8 Connections for external conductors
Is the panel builder's responsibility.
Connection type
Pre-wired connection (communication, NZM connection)
Push-In (supply connection, rated control voltage)
Parity
Even, uneven, unavailable (default)
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Special features
Baud Rates 9600, 19200, 38400, 57600 (default 19200)
For the Fieldbus connection.
The module is mounted in the right hand accessory pocket of the circuit breaker.
For connection to Modbus RTU.
RS485 interface
Cannot be used with the PXR10 NZM-AX electronic trip.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Type
Accessory
Communications module
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Used with
NZM2(3)(4)(-4)-VX(MX)(PX)(PMX)
Communication address range
001 - 247 (default 002)
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Fieldbus type
Customer-wired standard Modbus connection
Datasheet