Trade Price
£11.44
Per
1
Unit
EACH
Pack Quantity
Eaton Moeller series xPole - PLS6/M MCB. PLS6, 1-pole, tripping characteristic: B, rated current In: 20 A, rated switching capacity IEC/EN 60898-1: 6 kA
Product Length/Depth
85 mm
Product Height
73 mm
Product Width
17.5 mm
Product Weight
0.12 kg
Compliances
RoHS conform
Certifications
CE
Rated operational current for specified heat dissipation (In)
20 A
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
Rated short-circuit breaking capacity (EN 60898) at 230 V
6 kA
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Current limiting class
3
Rated short-circuit breaking capacity (EN 60898) at 400 V
6 kA
Amperage Rating
20 A
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
Frequency rating - max
60 Hz
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.8 Connections for external conductors
Is the panel builder's responsibility.
Rated short-circuit breaking capacity (IEC 60947-2) at 400 V
0 kA
Number of poles (total)
1
Rated short-circuit breaking capacity (IEC 60947-2) at 230 V
0 kA
Special features
Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
Ambient operating temperature - max
75 °C
Heat dissipation per pole, current-dependent
0 W
Built-in depth
70.5 mm
Rated switching capacity (IEC/EN 60898-1)
6 kA
Features
Additional equipment possible
Connectable conductor cross section (solid-core) - min
1 mm²
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Number of poles
Single-pole
Ambient operating temperature - min
-25 °C
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Used with
PLS6
Miniature circuit breaker
Equipment heat dissipation, current-dependent
3.2 W
Tripping characteristic
B
Frequency rating - min
50 Hz
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Static heat dissipation, non-current-dependent
0 W
Application
Switchgear for residential and commercial applications
xPole - Switchgear for residential and commercial applications
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Voltage type
AC
Number of poles (protected)
1
Heat dissipation capacity
0 W
Release characteristic
B
Width in number of modular spacings
1
Power loss
3.3 W
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Connectable conductor cross section (solid-core) - max
25 mm²
Degree of protection
IP20
Overvoltage category
III
Pollution degree
2
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
Connectable conductor cross section (multi-wired) - min
1 mm²
Rated impulse withstand voltage (Uimp)
4 kV
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Connectable conductor cross section (multi-wired) - max
25 mm²
Type
Miniature circuit breaker
PLS6
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
Rated operational voltage (Ue) - max
230 V
Rated insulation voltage (Ui)
440 V
Datasheet