NZM2/3-XA2A208-240AC

A shunt release,Relay,2NO,208-240AC,PI

Trade Price

£96.13

Per

1

Unit

EACH

Pack Quantity

NZM2/3-XA2A208-240AC
NZM2/3-XA2A208-240AC
NZM2/3-XA2A208-240AC
NZM2/3-XA2A208-240AC

Information

Eaton Moeller series NZM - Molded Case Circuit Breaker. Shunt release for NZM2/3, configurable relays, 2NO, 208-240AC, Push-in terminals

Technical Specifications

Product Length/Depth

115 mm

Product Height

65 mm

Product Width

75 mm

Product Weight

0.08 kg

Compliances

UL/CSA

IEC

RoHS conform

Certifications

CSA certified

CE marking

CSA-C22.2 No. 5-09

CSA (Class No. 1437-01)

CSA (File No. 22086)

UL (Category Control Number DIHS)

UL (File No. E140305)

IEC60947

UL489

UL listed

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

Terminal capacity (solid cable)

0.2 mm² - 1.5 mm² (1x) at shunt release

0.2 mm² - 1.5 mm² (1x) for undervoltage release

Rated control supply voltage (Us) at AC, 50 Hz - min

208 V

10.4 Clearances and creepage distances

Meets the product standard's requirements.

Minimum command time - min

10 ms

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

Rated control supply voltage (Us) at DC - min

0 V

Rated control supply voltage (Us) at AC, 50 Hz - max

250 V

10.8 Connections for external conductors

Is the panel builder's responsibility.

Minimum command time - max

15 ms

Special features

The breakers are actuated by a voltage pulse or by applying a no-break current.

For signalizing commands or different states of the circuit-breaker.

Two relays per unit.

The activation criteria can be configured in the trip unit.

Configuration via communication or circuit breaker display or front USB port and Eaton Power Xpert Protection Manager.

If the shunt trip is live, contact with the circuit breaker’s primary contacts is prevented when switched on.

Only for use in combination with circuit-breakers with electronic trips.

Shunt trip relay modules cannot be installed simultaneously with make-before-break auxiliary contact NZM...-XHIV, under-voltage trip NZM...-XU... or shunt trip NZM...-XA.

Relay coil is controlled by trip unit.

Relay contacts for control wiring.

Relays can be used for controlling remote operator with Us=208-204 V AC.

Control wiring on push-in clamps.

Cannot be used with the PXR10 NZM-AX electronic trip.

Voltage rating at AC (x Us) - min

.7

Rated control supply voltage (Us) at DC - max

0 V

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

Used with

PXR20(25) NZM3(-4)-..X…

PXR20(25) NZM2(-4)-..X…

Electric connection type

Screw connection

Voltage rating at AC (x Us) - max

1.1

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

Rated operational current

1 A (24 V AC-1, relay contacts)

1 A (110 V AC-1, relay contacts)

1 A (230 V AC-1, relay contacts)

Number of contacts (normally closed contacts)

0

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

Voltage type

AC

Terminal capacity (stranded cable)

0.25 mm² - 1.5 mm² (1x) for undervoltage release

0.25 mm² - 1.5 mm² (1x) at shunt release (insulated ferrule according to DIN46224 / 4)

0.25 mm² - 1.5 mm² (1x) at shunt release

24 - 16 AWG (1x) for undervoltage release

0.25 mm² - 0.75 mm² (1x) at shunt release (uninsulated ferrule according to DIN46228 / 1)

24 - 16 AWG (1x) at shunt release

Frame

NZM2/3

Reaction time

20 ms

Suitable for

Motor safety switch

Off-load switch

Pick-up power consumption (shunt release)

2.5 VA/W

Strip length

8 mm (relay contact connection)

Rated control voltage (relay contacts)

24 V DC

24 V AC

208 V AC

240 V AC

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

Time on duty - max

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

Connection type

With push in terminal

Voltage rating

0.7 - 1.1 x Us

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

Overvoltage category

III

Number of relays

2

Undelayed short-circuit release - min

0 A

Pollution degree

2

Rated control supply voltage (Us) at AC, 60 Hz - min

208 V

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

Rated impulse withstand voltage (Uimp)

4 kV AC

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

Switching capacity (reference value) - min

0.1 mA / 0.1 VDC

Type

Accessory

Shunt release

Shunt release with two relays

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.7 Inscriptions

Meets the product standard's requirements.

Rated control supply voltage (Us) at AC, 60 Hz - max

250 V

Number of contacts (normally open contacts)

2

Undelayed short-circuit release - max

0 A

Number of contacts (change-over contacts)

0

Rated insulation voltage (Ui)

250 V

Document Links

Datasheet