Trade Price
£882.53
Per
1
Unit
EACH
Pack Quantity
Eaton Moeller series NZM - Molded Case Circuit Breaker. Earth-fault release, 300mA, 4p, right
Product Length/Depth
220 mm
Product Height
80 mm
Product Width
135 mm
Product Weight
1.6 kg
Compliances
IEC
RoHS conform
Certifications
IEC/EN 60947-2
IEC/EN 60947-2 annex B
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Rated control supply voltage (Us) at AC, 50 Hz - min
200 V
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Mounting Method
On the right side
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
Rated fault current - max
0.3 A
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at AC, 50 Hz - max
415 V
Frequency rating
50 Hz / 60 Hz
10.8 Connections for external conductors
Is the panel builder's responsibility.
Special features
Earth-fault release to IEC/EN 60947-2
Not UL/CSA approved
Suitable for use in three-phase systems
Pulse-current sensitive type A according to core-balance principle
For 4 pole NZM1-4 circuit-breakers and N1-4 switch-disconnectors
Supply voltage-dependent Ue = 200 – 415 V 50/60 Hz
Control knobs, sealable.
Fitted on the right side up to In = 160 A at ICu = 50 kA
Sensitivity type
Pulse-current sensitive as per core-balance principle (type A)
Ambient operating temperature - max
40 °C
Power on-delay time - max
300 ms
Rated control supply voltage (Us) at DC - max
0 V
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Number of poles
Four-pole
Ambient operating temperature - min
-5 °C
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Used with
NZM1-4
Four-pole
N1-4
Mounting position
Vertical and 90° in all directions
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Application
In three-phase systems
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Frame
45 mm
NZM1
Power on-delay time - min
300 ms
Current rating - min
15 A
Fault current detection range
50/60 Hz
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
Lifespan, mechanical
20000 operations
Voltage rating
200 - 415 V AC, min. 80 V AC for detection of fault currents type A/AC (dependent on mains voltage)
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Degree of protection
IP20 (operating component area)
Rated control supply voltage (Us) at AC, 60 Hz - min
200 V
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
Terminal capacity (solid/flexible conductor)
As NZM1 standard terminal with ferrules
As NZM1 standard terminal without ferrules
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Type
Accessory
Earth-fault releases
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
Rated control supply voltage (Us) at AC, 60 Hz - max
415 V
Current rating - max
160 A
Rated operating voltage (Ue) - max
415 V
Rated fault current - min
0.3 A
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Datasheet