NZMH3-4-PX400/VAR-SVE

NZM,Energy met.cl1,400A,3p,plug-in conn.

Trade Price

£2,645.52

Per

1

Unit

EACH

Pack Quantity

NZMH3-4-PX400/VAR-SVE
NZMH3-4-PX400/VAR-SVE
NZMH3-4-PX400/VAR-SVE

Information

Eaton Moeller series NZM - Molded Case Circuit Breaker. NZM3 PXR25 circuit breaker - integrated energy measurement class 1, 400A, 4p, variable, plug-in technology, H, 3

Technical Specifications

Product Length/Depth

335 mm

Product Height

215.2 mm

Product Width

185 mm

Product Weight

9.42 kg

Compliances

RoHS conform

Certifications

IEC

IEC/EN 60947

Voltage rating

690 V - 690 V

Rated impulse withstand voltage (Uimp) at auxiliary contacts

6000 V

Rated impulse withstand voltage (Uimp) at main contacts

8000 V

Current rating of neutral conductor

0 - 60% - 100% of phase conductor

Rated short-time withstand current (t = 0.3 s)

3.3 kA

Rated short-time withstand current (t = 1 s)

3.3 kA

Amperage Rating

400 A

Instantaneous current setting (Ii) - min

2 A

Instantaneous current setting (Ii) - max

12 A

Overload current setting (Ir) - min

160 A

Overload current setting (Ir) - max

400 A

Short delay current setting (Isd) - min

2 A

Short delay current setting (Isd) - max

10 A

Short-circuit release delayed setting - min

320 A

Short-circuit release delayed setting - max

4000 A

Short-circuit release non-delayed setting - min

800 A

Short-circuit release non-delayed setting - max

4800 A

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz

150 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz

150 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz

130 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz

33 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz

9 kA

Rated short-circuit making capacity Icm at 240 V, 50/60 Hz

330 kA

Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz

330 kA

Rated short-circuit making capacity Icm at 440 V, 50/60 Hz

286 kA

Rated short-circuit making capacity Icm at 525 V, 50/60 Hz

143 kA

Rated short-circuit making capacity Icm at 690 V, 50/60 Hz

74 kA

Short-circuit total breaktime

< 10 ms

Electrical connection type of main circuit

Other

Isolation

300 V AC (between the auxiliary contacts)

500 V AC (between auxiliary contacts and main contacts)

Number of operations per hour - max

60

Handle type

Rocker lever

Utilization category

A (IEC/EN 60947-2)

Overvoltage category

III

Pollution degree

3

Lifespan, electrical

5000 operations at 400 V AC-1

3000 operations at 690 V AC-1

5000 operations at 415 V AC-1

Direction of incoming supply

As required

Mounting Method

Built-in device plug-in technique

Plug-in unit

Degree of protection

IP20 (basic degree of protection, in the operating controls area)

IP20

Degree of protection (IP), front side

IP40 (with insulating surround)

IP66 (with door coupling rotary handle)

Degree of protection (terminations)

IP00 (terminations, phase isolator and strip terminal)

IP10 (tunnel terminal)

Protection against direct contact

Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110

Shock resistance

20 g (half-sinusoidal shock 20 ms)

Number of auxiliary contacts (change-over contacts)

0

Number of auxiliary contacts (normally closed contacts)

0

Number of auxiliary contacts (normally open contacts)

0

Position of connection for main current circuit

Connection at separate chassis part

Climatic proofing

Damp heat, constant, to IEC 60068-2-78

Damp heat, cyclic, to IEC 60068-2-30

Lifespan, mechanical

15000 operations

Document Links

Datasheet