Trade Price
£147.07
Per
1
Unit
EACH
Pack Quantity
1
Eaton Moeller® series DILM Contactor, 3 pole, 380 V 400 V 18.5 kW, 220 V 50/60 Hz, AC operation, Screw terminals
Product Length/Depth
132.1 mm
Product Height
115 mm
Product Width
55 mm
Product Weight
0.872 kg
Compliances
CE Marked
Certifications
IEC 60947-4-1
UL 508
CSA Std. C22.2 No. 14-05
EN 60947-4-1
VDE
IEC/EN 60947
CSA-C22.2 No. 60947-4-1-14
UL Category Control No.: NLDX
CSA Class No.: 2411-03, 3211-04
UL
UL File No.: E29096
CSA
CE
CSA File No.: 012528
IEC/EN 60947-4-1
VDE 0660
UL 60947-4-1
Catalog Notes
Contacts according to EN 50012
Terminal capacity (flexible with ferrule)
2 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 35) mm², Main cables
2 x (0.75 - 25) mm², Main cables
1 x (0.75 - 2.5) mm², Control circuit cables
Rated operational current for specified heat dissipation (In)
40 A
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Rated operational power at AC-3, 380/400 V, 50 Hz
18.5 kW
Conventional thermal current ith (3-pole, enclosed)
45 A
Rated operational power at AC-4, 380/400 V, 50 Hz
9 kW
Rated operational current (Ie) at AC-4, 440 V
18 A
Terminal capacity (copper band)
2 x (6 x 9 x 0.8) mm (Number of segments x width x thickness), Main cables
Rated control supply voltage (Us) at AC, 50 Hz - min
220 V
Conventional thermal current ith at 60°C (3-pole, open)
50 A
10.4 Clearances and creepage distances
Meets the product standard's requirements.
Number of contacts (normally closed) as main contact
0
Short-circuit current rating (high fault at 480 V)
30/100 kA, Fuse, SCCR (UL/CSA)
250/150 A, Class J, max. Fuse, SCCR (UL/CSA)
100 A, max. CB, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
Conventional thermal current ith at 55°C (3-pole, open)
55 A
Rated operational power (NEMA)
22 kW
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
Ambient storage temperature - min
40 °C
Rated breaking capacity at 380/400 V
400 A
Short-circuit current rating (basic rating)
10 kA, SCCR (UL/CSA)
250 A, max. Fuse, SCCR (UL/CSA)
250 A, max. CB, SCCR (UL/CSA)
Rated control supply voltage (Us) at AC, 50 Hz - max
220 V
Rated breaking capacity at 660/690 V
250 A
Operating temperature
-25° to 60°C
Rated operational current (Ie) at DC-1, 220 V
45 A
Special purpose rating of elevator control
34 A, 480 V 60 Hz 3-ph, (UL/CSA)
25.3 A, 200 V 60 Hz 3-ph, (UL/CSA)
30 HP, 600 V 60 Hz 3-ph, (UL/CSA)
32 A, 600 V 60 Hz 3-ph, (UL/CSA)
10 HP, 240 V 60 Hz 3-ph, (UL/CSA)
7.5 HP, 200 V 60 Hz 3-ph, (UL/CSA)
25 HP, 480 V 60 Hz 3-ph, (UL/CSA)
28 A, 240 V 60 Hz 3-ph, (UL/CSA)
Ambient operating temperature - max
60 °C
Assigned motor power at 115/120 V, 60 Hz, 1-phase
3 HP
Rated operational power at AC-4, 440 V, 50 Hz
10 kW
Electrical connection type of main circuit
Screw connection
Number Of Poles
Three-pole
Ambient operating temperature - min
-25 °C
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Application
Contactors for Motors
Operating frequency
5000 mechanical Operations/h (AC operated)
Voltage type
AC
Short-circuit protection rating (type 1 coordination) at 400 V
125 A gG/gL
Product category
Contactors
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V
18 A
Rated operational power at AC-3, 690 V, 50 Hz
23 kW
Power consumption, pick-up, 50 Hz
154 VA, Dual-frequency coil in a cold state and 1.0 x Us
168 VA, Dual-frequency coil in a cold state and 1.0 x Us
Heat dissipation capacity Pdiss
0 W
Assigned motor power at 460/480 V, 60 Hz, 3-phase
30 HP
Special purpose rating of tungsten incandescent lamps
74 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
74 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
Switching time (AC operated, make contacts, opening delay) - min
8 ms
Rated operational current (Ie) at AC-4, 500 V
18 A
Rated operational power at AC-3, 240 V, 50 Hz
13.5 kW
Operating voltage at AC, 60 Hz - max
690 V
Terminal capacity (solid/stranded AWG)
18 - 14, Control circuit cables
Single 14 - 1, double 14 - 2, Main cables
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Degree of protection
IP00
Overvoltage category
III
Switching time (AC operated, make contacts, opening delay) - max
13 ms
Ambient storage temperature - max
80 °C
Pollution degree
3
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V
60 A
Power consumption, pick-up, 60 Hz
168 VA, Dual-frequency coil in a cold state and 1.0 x Us
154 VA, Dual-frequency coil in a cold state and 1.0 x Us
Switching time (AC operated, make contacts, closing delay) - max
18 ms
Rated impulse withstand voltage (Uimp)
8000 V AC
Connection
Screw terminals
Operating voltage at AC, 60 Hz - min
230 V
Tightening torque
3.3 Nm, Screw terminals, Main cables
1.2 Nm, Screw terminals, Control circuit cables
Rated operational power at AC-4, 660/690 V, 50 Hz
12 kW
Frame size
FS3
Conventional thermal current ith (1-pole, enclosed)
112 A
Rated operational current (Ie) at AC-3, 660 V, 690 V
25 A
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
40 A
Switching time (AC operated, make contacts, closing delay) - min
12 ms
Short-circuit protection rating (type 2 coordination) at 400 V
63 A gG/gL
Special purpose rating of ballast electrical discharge lamps
79 A (480V 60Hz 3phase, 277V 60Hz 1phase)
79 A (600V 60Hz 3phase, 347V 60Hz 1phase)
Number of auxiliary contacts (normally open contacts)
0
Rated operational power at AC-3, 500 V, 50 Hz
28 kW
Shock resistance
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
Rated operational current (Ie) at DC-1, 110 V
50 A
Assigned motor power at 230/240 V, 60 Hz, 3-phase
15 HP
Drop-out voltage
AC operated: 0.6 - 0.3 x UC, AC operated
Power consumption, sealing, 60 Hz
14 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
22 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
4.1 W, Dual-frequency coil in a cold state and 1.0 x Us
Resistance per pole
1.9 mΩ
Ambient operating temperature (enclosed) - min
25 °C
Stripping length (control circuit cable)
10 mm
Operating voltage at AC, 50 Hz - max
690 V
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Amperage Rating
40A
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
Stripping length (main cable)
14 mm
Ambient operating temperature (enclosed) - max
40 °C
Special purpose rating of resistance air heating
79 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
79 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
Rated control supply voltage (Us) at DC - min
0 V
Short-circuit current rating (high fault at 600 V)
30/100 kA, Fuse, SCCR (UL/CSA)
30 kA, CB, SCCR (UL/CSA)
250 A, max. CB, SCCR (UL/CSA)
250/150 A, Class J, max. Fuse, SCCR (UL/CSA)
Frequency rating
50-60 Hz
10.8 Connections for external conductors
Is the panel builder's responsibility.
Number of main contacts (normally open contact)
3
Rated breaking capacity at 220/230 V
400 A
Screw size
M6, Terminal screw, Main cables
M3.5, Terminal screw, Control circuit cables
Rated operational current (Ie) at AC-4, 400 V
18 A
Short-circuit protection rating (type 2 coordination) at 690 V
50 A gG/gL
Assigned motor power at 575/600 V, 60 Hz, 3-phase
40 HP
Protection
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Power consumption, sealing, 50 Hz
4.1 W, Dual-frequency coil in a cold state and 1.0 x Us
Rated operational power at AC-3, 440 V, 50 Hz
25 kW
Terminal capacity (stranded)
2 x (16 - 35) mm², Main cables
1 x (16 - 50) mm², Main cables
Rated breaking capacity at 500 V
400 A
Rated operational power at AC-3, 415 V, 50 Hz
24 kW
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Emitted interference
According to EN 60947-1
Connection to SmartWire-DT
No
Static heat dissipation, non-current-dependent Pvs
4.1 W
Rated control supply voltage (Us) at DC - max
0 V
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Utilization category
AC-3: Normal AC induction motors: starting, switch off during running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Rated operational current (Ie) at AC-3, 440 V
40 A
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Safe isolation
440 V AC, Between coil and contacts, According to EN 61140
440 V AC, Between the contacts, According to EN 61140
Operating voltage at AC, 50 Hz - min
230 V
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Heat dissipation per pole, current-dependent Pvid
2.2 W
Actuating voltage
220 V 50/60 Hz
Operating temperature - min
-25 °C
Rated operational current (Ie) at AC-4, 660 V, 690 V
14 A
Equipment heat dissipation, current-dependent Pvid
6.6 W
Assigned motor power at 200/208 V, 60 Hz, 3-phase
10 HP
Pick-up voltage
0.8 - 1.1 V AC x Uc
Suitable for
Also motors with efficiency class IE3
Conventional thermal current ith at 40°C (3-pole, open)
60 A
Terminal capacity (solid)
2 x (0.75 - 16) mm², Main cables
1 x (0.75 - 4) mm², Control circuit cables
1 x (0.75 - 16) mm², Main cables
2 x (0.75 - 2.5) mm², Control circuit cables
Number of auxiliary contacts (normally closed contacts)
0
Interference immunity
According to EN 60947-1
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
Operating temperature - max
60 °C
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
Lifespan, mechanical
7,000,000 Operations (Coil 50/60 Hz)
10,000,000 Operations (AC operated)
Short-circuit protection rating (type 1 coordination) at 690 V
80 A gG/gL
Rated making capacity up to 690 V (cos phi to IEC/EN 60947)
560 A
Rated operational power at AC-4, 240 V, 50 Hz
5.5 kW
Rated operational power at AC-4, 500 V, 50 Hz
11 kW
Voltage rating
220 V
Rated operational current (Ie) at DC-1, 60 V
50 A
Rated operational power at AC-4, 220/230 V, 50 Hz
5 kW
Rated operational voltage (Ue) at AC - max
690 V
Rated control supply voltage (Us) at AC, 60 Hz - min
220 V
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Switching capacity (main contacts, general use)
63 A, Maximum motor rating (UL/CSA)
Conventional thermal current ith at 50°C (3-pole, open)
57 A
Rated operational current (Ie) at AC-3, 500 V
40 A
Assigned motor power at 230/240 V, 60 Hz, 1-phase
7.5 HP
Screwdriver size
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver
2, Terminal screw, Pozidriv screwdriver
Duty factor
100 %
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V
40 A
Conventional thermal current ith of main contacts (1-pole, open)
125 A
Rated control supply voltage (Us) at AC, 60 Hz - max
220 V
Arcing time
10 ms
Rated operational power at AC-4, 415 V, 50 Hz
9.5 kW
Rated insulation voltage (Ui)
690 V
Altitude
Max. 2000 m
Datasheet