Trade Price
£383.34
Per
1
Unit
EACH
Pack Quantity
1
Eaton Moeller series NZM - Molded Case Circuit Breaker. Earth-leakage circuit-breaker 0, 03-5 A
Product Length/Depth
80 mm
Product Height
45 mm
Product Width
95 mm
Product Weight
0.192 kg
Compliances
IEC
RoHS conform
Certifications
IEC 1009
IEC 1008
IEC 755
IEC/EN 60947-2
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Rated control supply voltage (Us) at AC, 50 Hz - min
184 V
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Mounting Method
Snap fixing, top-hat rail DIN 46277, IEC/EN 60715
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
Rated fault current - max
5 A
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at AC, 50 Hz - max
276 V
10.8 Connections for external conductors
Is the panel builder's responsibility.
Terminal protection
Finger/back-of-hand proof to BGV A2, VDE 106 part 100
Special features
Adjustable fault current and delay time
Fault current early warning by flashing, red LED
Pulse-current sensitive
Integrated auxiliary contact (1 C/O)
Ring-type transformer must also be ordered
not UL/CSA approved
Sensitivity type
Pulse current sensitive, type A
Ambient operating temperature - max
50 °C
Power on-delay time - max
5000 ms
Features
Sealable, setting buttons
1 integrated changeover contact (relay contact)
Rated control supply voltage (Us) at DC - max
0 V
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Ambient operating temperature - min
-10 °C
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Voltage rating of relay contact
250 V AC / 100 V DC
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Frame
45 mm
NZM1/2/3/4
Power on-delay time - min
5000 ms
Device width
85 mm
Terminals (top and bottom)
Box terminals
Delay time
0.02, 0.1, 0.3, 0.5, 1, 3, 5 ms
Power consumption
3 W
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
Current rating of relay contact
6 A
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Rated control supply voltage (Us) at AC, 60 Hz - min
184 V
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
Terminal capacity (solid/flexible conductor)
0.75 mm² - 1.5 mm² (2x) with ferrules
0.75 mm² - 2.5 mm² (2x) solid, 0.75 mm² - 1.5 mm² (2x) flexible/with ferrules
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Functions
Delay adjustable
Type
Accessory
Residual current relays
Voltage release
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
Rated control supply voltage (Us) at AC, 60 Hz - max
276 V
Rated operating voltage (Ue) - max
276 V
Rated fault current - min
0.03 A
Datasheet