EAM1002RH

RCCB 100A DP 30mA Type AC

Trade Price

£254.95

Per

1

Unit

EACH

Pack Quantity

1

EAM1002RH

Information

Eaton Moeller series xPole UK - EAM RCCB. Residual current circuit-breaker, 100 A, 2-pole, 30mA, Type AC, RH

Technical Specifications

Product Length/Depth

80 mm

Product Height

71 mm

Product Width

35 mm

Product Weight

0.22 kg

Compliances

RoHS conform

Certifications

IEC/EN 61008

Application

Switchgear for residential and commercial applications

Number of poles

Two-pole

Tripping time

Non-delayed

Amperage Rating

100 A

Rated short-circuit strength

10 kA

Fault current rating

30 mA

Sensitivity type

AC current sensitive

Impulse withstand current

Partly surge-proof 250 A

Type

EAM

Residual current circuit breakers

Type AC

Voltage rating

230 V AC

Rated operational voltage (Ue) - max

230 V

Rated insulation voltage (Ui)

440 V

Rated impulse withstand voltage (Uimp)

4 kV

Rated fault current - min

0.03 A

Rated fault current - max

0.03 A

Frequency rating

50 Hz

Short-circuit rating

63 A (max. admissible back-up fuse)

Leakage current type

AC

Rated residual making and breaking capacity

1000 A

Admissible back-up fuse overload - max

25 A gG/gL

Rated short-time withstand current (Icw)

10 kA

Surge current capacity

0.25 kA

Test circuit range

196 V AC - 264 V AC

Pollution degree

2

Lifespan, electrical

4000 operations

Frame

45 mm

Width in number of modular spacings

2

Built-in width (number of units)

35 mm (2 SU)

Built-in depth

70.5 mm

Mounting Method

IEC/EN 60715 top-hat rail

DIN rail

Degree of protection

IP20

IP40, IP54 (with moisture-proof enclosure)

Terminals (top and bottom)

Box clamp

Terminal capacity (solid wire)

1.5 mm² - 35 mm²

Connectable conductor cross section (solid-core) - min

1.5 mm²

Connectable conductor cross section (solid-core) - max

35 mm²

Connectable conductor cross section (multi-wired) - min

1.5 mm²

Connectable conductor cross section (multi-wired) - max

16 mm²

Terminal protection

Finger and hand touch safe, DGUV VS3, EN 50274

Busbar material thickness

0.8 mm - 2 mm

Lifespan, mechanical

20000 operations

Permitted storage and transport temperature - min

-35 °C

Permitted storage and transport temperature - max

60 °C

Climatic proofing

25-55 °C / 90-95% relative humidity according to IEC 60068-2

Rated operational current for specified heat dissipation (In)

100 A

Heat dissipation per pole, current-dependent

0 W

Equipment heat dissipation, current-dependent

13.6 W

Static heat dissipation, non-current-dependent

0 W

Heat dissipation capacity

0 W

Ambient operating temperature - min

-25 °C

Ambient operating temperature - max

60 °C

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions

Meets the product standard's requirements.

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

10.8 Connections for external conductors

Is the panel builder's responsibility.

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Features

Additional equipment possible

Residual current circuit breaker

Fitted with:

Interlocking device

Special features

Maximum operating temperature is 60 °C: Starting at 40 °C, the max. permissible continuous current decreases by 3% for every 1 °C

Used with

Residual current circuit breakers

EAM

Type AC

Document Links

Datasheet