Trade Price
£275.06
Per
1
Unit
EACH
Pack Quantity
1
Exceeds the requirements of EN 60947-2
Three-pole MCCBs have adjustable thermal and fixed magnetic overloads
Thermal overload adjusts to 1 x In, 0.8 x In and 0.63 x In
Ultimate breaking capacity: 40kA at 415V AC
Cable connection: Via cable clamps and maximum cable termination is 70mm²
Rated insulation voltage: 690V AC (Ui)
Max current rating: 80A
Min current rating: 50A