NHPBLAR1

Main Unit Lightning Arrester Kit - Type 1

Trade Price

£1,747.86

Per

1

Unit

EACH

Pack Quantity

NHPBLAR1

Information

• Accessory for NH250 Panel Boards • Supplied with J-Frame MCCB (for SPD protection), cable loom kit & SPD mounting bracket • 18th edition compliant • Fits into dedicated knock-out slot in panel board. MCCB utilises bottom left-hand Way. • Nominal Voltage (AC) 240/415

Technical Specifications

System configuration DC

No

System configuration IT

No

System configuration TN

No

System configuration TN-C

No

System configuration TN-C-S

No

System configuration TN-S

Yes

System configuration TT

Yes

System configuration other

No

Number of conductors (without earthing)

4

Nominal discharge surge current (8/20)

25 kA

Short-circuit breaking capacity (Isccr)

50 kA

Max. continuous voltage AC

350 V

Max. discharge surge current (8/20)

100 kA

Mounting method

DIN rail (top hat rail) 35 mm

Construction size

8 modular spacing

Voltage protection level

1.5 kV

Max. conductor cross section solid (solid, stranded)

35 mm²

Max. conductor cross section flexible (fine-strand)

25 mm²

With remote signalling contact

Yes

Integrated backup fuse

No

Signalling at the device

Optic

Category type 2

No

Degree of protection (IP)

IP20

Product Standard/s

BS EN 61643-11

Terminal Capacity L&N

25 mm²

Terminal Capacity E

25 mm²

Frequency

50/60 Hz

CE Conformity

Yes

WEEE Symbol

Yes

UKCA Conformity

Yes

Document Links

Datasheet