Pack Quantity
BSI certified to EN54-13 (Fire detection and fire alarm systems, compatibility assessment of system components). Fits inside a CFP standard 2-8 zone fire panel to provide two EN54-13 monitored sounder circuits. When used in conjunction with our CFP Standard 2-8 Zone Fire Panels, ActiV fire detectors and a wide range of specified sounders, VADs and call points, installers can rest-assured the system they are installing is fully compliant with the system compatibility requirements of EN54-13 and is certified as such by the BSI. Monitors its onboard sounder circuits for partial and full open or short circuit faults when used in conjunction with a BF355 fault monitoring module (one BF355 required per sounder circuit). Ideal for use in territories where EN54-13 is mandated such as Germany, the Netherlands and Belgium.
Approvals/certifications
Certified to EN54-13 by the BSI (KM615562).
Application/operation
Detects sounder circuit resistances down to 10Ω plus or minus 10%.
No. of conventional sounder circuits
2.
EOL resistor value
6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
Alarm voltage
27 VDV max., 20 VDC min
Max. sounder output current
2 x 400mA (800mA total)
Product dimensions (mm)
80 W x 124 H x D 9mm.