Trade Price
£59.20
Per
1
Unit
EACH
Pack Quantity
Third-party certified to EN54-3 (Sounders) and EN54-23 (VADs). Provides ‘C-3-8.5’ light distribution (min 0.4 lux over a 3 x 8.5m cylindrical area). Impressive 96dB(A) sound output @ 1m. Includes 31 selectable primary tones and an optional secondary tone. Two volume levels (high and low) Three selectable VAD flash rates (0.5Hz, 1Hz, OFF) Alarm Current at 30Vdc = 12.2mA (0.5Hz) or 19.5mA (1Hz) Alarm Current at 18Vdc = 14.5mA (0.5Hz) or 25mA (1Hz) Optional BF330CTLIDW white or BF330CTLIDR red cap available for stand-alone use. Supplied with a BF431QCP quick connect plate and detector spur wires. IP21C rated.
Approvals/certifications
Certified to EN54-3 & 23 by the LPCB & VdS.
Protocol/compatibility
Compatible with C-TEC's CFP, FP, MFP and EP203 conventional fire alarm panels and virtually all other makes (testing on third-party panels is recommended before use)
Application/operation
Designed to be ceiling mounted – either stand-alone with a red or white cap or as part of a stacked Sounder/VAD/Detector Base combination.
VAD category & coverage
C-3-8.5 (151m3 cylindrical coverage).
Flash rate & colour
0.5Hz; 1Hz or OFF / White.
Supply/operating voltage
18 to 30V DC.
Nominal SPL (Sound Pressure Level)
96dB(A).
Alarm current
At 30Vdc: 12.2mA (0.5Hz) or 19.5mA (1Hz); At 18Vdc: 14.5mA (0.5Hz) or 25mA (1Hz)
Product dimensions (mm)
122mm diameter x 46mm deep (not including optional detector and base).
IP Rating
IP21C (Type A).
Weight
170g.
Operating conditions/temperature
-10ºC to +55ºC. Max. 95% RH (Non-condensing).
Notes
For compliance to EN54-3 & EN54-23, the BF431QCP Quick Connect Plate must be used with the base device.
Lux level in area requiring coverage
Ceiling Mounted Direct Viewing
000-101 lux
8.3m H x 23.8m W
101-200 lux
7.2m H x 20.4m H
201-300 lux
5.7m H x 16.1m W
301-400 lux
4.2m H x 11.9m W
401-500 lux
3.3m H x 9.3m W
501-600 lux
2.7m H x 7.6m W
601-700 lux
2.1m H x 5.9m W
701-800 lux
1.5m H x 4.2m W
Datasheet