Z15

ZFP 4 Way Conventional Sounder Circuit PCB (full size)

Trade Price

£307.36

Per

1

Unit

EACH

Pack Quantity

Z15

Information

Adds four additional 1A 6K8 conventional sounder circuits to a ZFP addressable fire panel. All circuits fully monitored and programmable via the ZFP’s PC Tools. Requires a separate EN54-4 PSU mounted external to the panel. Programmable via the ZFP’s PC Tools. Polling, Power and separate Sounder Circuit activated indicators. Up to 15 A-BUS Expansion PCBs can be connected to a ZFP Panel via its RS485 A-BUS network. Typically installed within the ZFP panel but can work up to 1 KM away for non-EN 54-2 functions.

Technical Specifications

Type

4 x 1A 6K8 conventional sounder circuits.

Indicators

Polling LED; Power LED; Sounder Circuit Activated LEDs (x4).

Connections

A-BUS RS485 connections (B, A, 0) to main ZFP PCB; 24V supply input (from main ZFP PCB or external EN54-4 PSU); Comms and Power In/Out connections. Four x 1A 6K8 conventional sounder circuit connec

Product dimensions (mm)

67 W x 165 H x 17 D mm.

Weight

TBC.

Operating conditions/temperature

-5ºC to +40ºC. Max relative humidity: 95%.

Network specification

Dedicated A-BUS RS485 monitored radial circuit. 1KM max length. Up to 15 A-BUS PCBs per panel.

Document Links

Catalogue page

Datasheet