SAP501E/CA

SAP 1 Loop 16 Zone Addressable Sprinkler Monitoring Panel (C-TEC CAST protocol)

Trade Price

£496.05

Per

1

Unit

EACH

Pack Quantity

SAP501E/CA

Information

Ideal for monitoring up to 255 sprinkler flow switches. One CAST CA730 input output unit required per monitored flow switch. Utilises the same technology as C-TEC’s popular XFP addressable fire panel. Up to 16 sprinkler zone indicators available (assignable via the panel’s PC programming tools). Attractive flush or surface mountable plastic enclosure. Combined keypad or keyswitch entry.

Technical Specifications

Protocol/compatibility

C-TEC CAST.

Mains supply

230V 50/60Hz.

Mains rated current

350mA maximum.

Internal power supply

27Vdc nominal.

Total output current limited to

1.4A @ 230Vac (Imax.A 210mA; Imin. 40mA).

Quiescent current

50mA (loop unloaded).

Max battery size and type

2 x 12V 3.2Ah VRLA connected in series.

No. of loop drivers

1.

Max. loop output current

500mA (40V max).

Max. loop length

1KM.

Max. addressable devices per loop

255.

No. of conventional sounder circuits

2 (Max. length per circuit is 500m).

EOL resistor value

6800Ω 5% Tol. 0/25W (blue, grey, red, gold).

Max. sounder output current

400mA.

Auxiliary relays

3 x Programmable Relays (programmable from C&Es). 1 x Fault Relay (active when no faults are present). Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc.

Other outputs

24V Aux. Power (19.5V min, 28V max). Protected by a resettable fuse. Max. current 100mA.

Auxiliary inputs

2 x Programmable Inputs (programmable from C&Es). Connect to 0V to trigger, Max. input voltage 27V (non-latching).

PC connection

PC connection via RS232 molex connector (supplied in XFP507 upload/download software kit); No printer connection available.

Indicators

2 line x 40 character backlit display; 16 Zonal LEDs, General Fire; Energised; Pre-Alarm; Remote Output Activated; Remote Output Disabled; Accessed; Disablement; Test; Silenced; General Fault; Syst

Connections

Fixed, largest acceptable conductor size 1mm2.

Expansion connections

2-wire RS485 non-redundant network/repeater connection available via optional XFP761 network card. Max. 8 mains per network or 8 repeaters per non-networked main. Limit 1KM (main panel network) or

Product dimensions (mm)

380 W x 235 H x D 96mm (hole required for flush mounting = 367 W x 220 H x 75 D mm. No bezel required).

Construction & finish

Plastic lid and base; RAL7035 textured

IP Rating

IP30.

Weight

1.8kg (without batteries).

Operating conditions/temperature

-5ºC to +40ºC. Max relative humidity: 95%.

Product dimensions:

380 W x 235 H x 96 D mm. 

Hole required for flush mounting:

367 W x 220 H x 75 D mm. No bezel required.