Trade Price
£35.18
Per
1
Unit
EACH
Pack Quantity
LPCB certified to EN54-3 & 17 and Kiwa Telefication certified to EN54-13. Impressive 92dB(A) sound output @ 1m. Onboard short-circuit loop isolator. 5.5mA typical alarm current (460µA typical quiescent current) @ 24-40V DC. Group addressing facility allows multiple devices to be operated simultaneously. 4 selectable volume levels and 31 selectable tones. Optional BF330CTLIDW white or BF330CTLIDR red cap available for stand-alone use. IP21C rated. White ceiling fixing plate & detector spur wires included. ‘CAST’ is the world’s most-advanced ‘distributed intelligence’ fire alarm system protocol. Conceived, designed and realised by C-TEC as part of a five-year, multi-million pound project, it involved the creation of a powerful proprietary communication protocol (C-TEC Addressable System Technology, CAST) and multiple control panels & field devices. Now available to purchase, its key features include: * 255 devices per loop. * Autonomous decision-making for faster response times. * Multiple type codes. * 40V loop drive voltage. * Two ‘soft’ addressing options – automatic via the panel or manual via a powerful handheld programmer. * Powerful multi-level addressing facilitates easy device addition and swapped device identification. * Multiple functionality at a single address (integrated devices) – coming soon. * Volumes, tones & detector modes can be changed at compatible panels. * High-speed data transmission and robust data transfer. * Intrinsically EN54-13 compliant. * Provides geographical location of short and open circuit faults (a short circuit isolator is included as standard in every CAST field device). * Replace device function. * Future seamless integration with other CAST life safety systems reducing energy, servicing, installation and repair costs. * Designed and manufactured in the UK.
Approvals/certifications
LPCB certified to EN54-3 & 17 and Kiwa Telefication certified to EN54-13
Protocol/compatibility
Compatible with C-TEC's CAST protocol Addressable Fire Panels.
Application/operation
Designed to be ceiling mounted – either stand-alone with a red or white cap or as part of a stacked Sounder/Detector Base combination.
Supply/operating voltage
24 to 40V DC.
Quiescent current
460µA @ 24 to 40V DC (typical).
Nominal SPL (Sound Pressure Level)
92dB(A) when set to tone 1.
Alarm current
5.5mA @ 24 to 40V DC (typical, sounder on max).
Indicators
Polling (red LED).
Product dimensions (mm)
122mm diameter x 46mm deep (not including optional CAST detector and base).
IP Rating
IP21C (Type A).
Weight
170g.
Operating conditions/temperature
-10ºC to +55ºC. Max. 95% RH (Non-condensing).
Datasheet