CA430A/SR

CAST Hi-Output 100dB(A) Wall Sounder (shallow base)

Trade Price

£50.10

Per

1

Unit

EACH

Pack Quantity

CA430A/SR

Information

LPCB certified to EN54-3 & 17 and Kiwa Telefication certified to EN54-13. Impressive 100dB(A) sound output @ 1m. Onboard short-circuit loop isolator. 6.5mA typical alarm (460µA typical quiescent current) @24-40V DC (Sounder on max). Group addressing facility allows multiple devices to be operated simultaneously. 4 selectable volume levels and 31 selectable tones. IP21C (Type A) rated. ‘CAST’ is the world’s most-advanced ‘distributed intelligence’ fire alarm system protocol. Conceived, designed and realised by C-TEC as part of a five-year, multi-million pound project, it involved the creation of a powerful proprietary communication protocol (C-TEC Addressable System Technology, CAST) and multiple control panels & field devices. Now available to purchase, its key features include: * 255 devices per loop. * Autonomous decision-making for faster response times. * Multiple type codes. * 40V loop drive voltage. * Two ‘soft’ addressing options – automatic via the panel or manual via a powerful handheld programmer. * Powerful multi-level addressing facilitates easy device addition and swapped device identification. * Multiple functionality at a single address (integrated devices) – coming soon. * Volumes, tones & detector modes can be changed at compatible panels. * High-speed data transmission and robust data transfer. * Intrinsically EN54-13 compliant. * Provides geographical location of short and open circuit faults (a short circuit isolator is included as standard in every CAST field device). * Replace device function. * Future seamless integration with other CAST life safety systems reducing energy, servicing, installation and repair costs. * Designed and manufactured in the UK.

Technical Specifications

Approvals/certifications

LPCB certified to EN54-3 & 17 and Kiwa Telefication certified to EN54-13

Protocol/compatibility

Compatible with C-TEC's CAST protocol Addressable Fire Panels.

Application/operation

Designed to be wall mounted. Indoor areas only.

Supply/operating voltage

24 to 40V DC.

Quiescent current

460µA typical.

Nominal SPL (Sound Pressure Level)

100dB(A) when set to tone 1.

Alarm current

6.5mA typical @ 24-40V DC (Sounder on max).

Indicators

Polling (red LED).

Product dimensions (mm)

108mm diameter x 99mm deep

IP Rating

IP21C (Type A).

Weight

215g.

Operating conditions/temperature

-10ºC to +55ºC. Max. 95% RH (Non-condensing).

Document Links

Catalogue page

Datasheet