Trade Price
£88.00
Per
Unit
Pack Quantity
Multiple functionality in a single device – CO fire, smoke & heat multisensor fire detection plus a 92db(A) tone Alarm sounder – detects real fires quickly, reduces false alarms effectively and indicates true alarm conditions decisively. Certified to EN54-3, 5, 7, 17, 29 & 31. Compatible with C-TEC’s ZFP touchscreen-controlled CAST protocol addressable fire panel. MASC™ (Miniature Advanced Smoke Detection Chamber) and AFFIRM™ algorithms provide incredible tolerance to false alarms whilst enhancing the detection of real fire conditions. Drift compensation functionality. Onboard short circuit loop isolator. Includes two 8mm x 2mm ultra-bright red LED indicating strips. Multiple detection modes and different sensitivities for different times of the day. 5.4mA max. alarm current (max volume). 630uA typical quiescent current @ 40V DC. Compatible with C-TEC’s CA408 CAST base c/w integrated locking mechanism & ID tag.
Approvals/certifications
CPR number 0063-CPR-242190012
Compatibility
Compatible with C-TEC's ZFP CAST Addressable Fire Alarm Systems
Type
CO, Heat & Smoke Fire Detection plus Tone Alarm.
Sensitivity
12 Detection Modes (default for this device is Mode 10).
Supply wiring
2-wire, polarity sensitive.
Supply/operating voltage
28 to 40V DC.
Quiescent current
630uA @ 40V.
VAD category & coverage
N/A.
Indicators
2 LED indicator strips emitting red light when in alarm offering 360º visibility. Optional remote LED.
Connections
Via CA408 base: 1 +Ve IN (analogue switch); 2 +Ve OUT (analogue switch); 3 Remote LED +Ve; 4 0V; 5 0V; 6 Screen; 7 Screen.
Product dimensions (mm)
105mm diameter x 48mm deep (detector only); 105mm diameter x 65mm deep (detector in base).
IP Rating
IP21C
Weight
125g (not in base); 180g (in base).
Operating conditions/temperature
-10ºC to +50ºC. Max relative humidity: 95% (non-condensing)
Notes
Requires a CA408 CAST base. CA408R relay base also available.
Datasheet