A programmable CAST-PRO heat detector. Certified to EN54-5 & 17 Compatible with C-TEC’s ZFP touchscreen-controlled CAST protocol addressable fire panel. Onboard short circuit loop isolator. Includes two 8mm x 2mm ultra-bright red LED indicating strips. Three operation modes – can be programmed to operate as an A1R, A2 or B heat detector. <1mA alarm current. 570A typical quiescent current @ 40V DC. Compatible with C-TEC’s CA408 CAST base c/w integrated locking mechanism & ID tag.
Approvals/certifications
CPR number 0063-CPR-242190023
Compatibility
Compatible with C-TEC's ZFP CAST Addressable Fire Alarm Systems
Type
Class A1R, Class A2 or Class B Heat (Programmable).
Sensitivity
3 Detection Modes (class A1R, A2 or B heat, default is Class A2).
Supply wiring
2-wire, polarity sensitive.
Supply/operating voltage
22 to 40V DC.
Quiescent current
570uA @ 40V.
VAD category & coverage
N/A.
Indicators
2 LED indicator strips emitting red light when in alarm offering 360º visibility. Optional remote LED.
Connections
Via CA408 base: 1 +Ve IN (analogue switch); 2 +Ve OUT (analogue switch); 3 Remote LED +Ve; 4 0V; 5 0V; 6 Screen; 7 Screen.
Product dimensions (mm)
105mm diameter x 48mm deep (detector only); 105mm diameter x 65mm deep (detector in base).
IP Rating
IP21C
Weight
118g (not in base); 172g (in base).
Operating conditions/temperature
-10ºC to +50ºC. Max relative humidity: 95% (non-condensing)
Notes
Requires a CA408 CAST base. CA408R relay base also available.