55000-835APO

AlarmSense Relay Module

Trade Price

£67.00

Per

1

Unit

EACH

Pack Quantity

55000-835APO

Information

Allows devices such as vibrating pillow alarms or vibrating radio/paging devices to be connected to an AlarmSense system.  Can also be used to monitor and switch conventional sounders and visual indicators. Suitable for use with C-TEC’s CFP AlarmSense range of 2-8 Zone Two-Wire Fire Panels. Operates in three configurations:- (1) relay activation places the AlarmSense Zone voltage across the output terminals. (2) relay activation reverses the polarity of the AlarmSense Zone voltage across the output terminals (to allow the use of monitored conventional sounders fitted with series diodes). (3) Two sets of volt-free contacts for use with door closure units, etc. Relay can be set to priority or non-priority by means of a DIL switch.

Technical Specifications

Protocol/compatibility

Suitable for use with C-TEC's CFP AlarmSense range of 2-8 Zone Two-Wire Fire Panels.

Supply/operating voltage

9 to 33V DC. (Relay operation voltage less than 18V; Relay reset voltage less than 15V).

Quiescent current

20µA.

Product dimensions (mm)

65 W x 45 H x 25 D mm.

IP Rating

TBC.

Weight

35g.

Properties

Relay contact ratings 1A @ 30VDC.

Operating conditions/temperature

-40ºC to +70ºC.

Notes

Alarm relay resets on silence.

Document Links

Datasheet