ESP RTDQ DATA SPD FOR THREE 3-WIRE RTD SYSTEMS SPACE SAVING DESIGN

Technical Specifications

Standards:

IEC 61643-21

Suitable For:

To protect systems against transient overvoltages or surges from lightning and electrical switching events

Nominal AC Voltage of the System (Uo):

6 V

Voltage Protection Level ( Up):

10 V

Maximum Continuous Operating Voltage (Uc):

7.79 V

Rated Current (In):

700 mA

Discharge Current:

I (max, 8 / 20 µs) 10 kA

Rated Frequency (f):

800 kHz

Number of Protected Poles:

3

Connection Type:

Screw Clamp

Serial Resistance:

1 Ω

Wire Stripping Length:

8 mm

RoHS Status:

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Ambient Air Temperature:

Operation -40 ... +80 °C

Width in Number of Modular Spacings:

1

Product Net Width:

95 mm

Product Net Height:

87 mm

Product Net Depth / Length:

18 mm

Product Net Weight:

.100 kg

Package Level 1 Units:

1 piece

WEEE Category:

5. Small Equipment (No External Dimension More Than 50 cm)

WEEE B2C / B2B:

Business To Business

CN8:

8536304000