Trade Price
POA
Per
Unit
Pack Quantity
ESP RTDQ DATA SPD FOR THREE 3-WIRE RTD SYSTEMS SPACE SAVING DESIGN
Standards:
IEC 61643-21
Suitable For:
To protect systems against transient overvoltages or surges from lightning and electrical switching events
Nominal AC Voltage of the System (Uo):
6 V
Voltage Protection Level ( Up):
10 V
Maximum Continuous Operating Voltage (Uc):
7.79 V
Rated Current (In):
700 mA
Discharge Current:
I (max, 8 / 20 µs) 10 kA
Rated Frequency (f):
800 kHz
Number of Protected Poles:
3
Connection Type:
Screw Clamp
Serial Resistance:
1 Ω
Wire Stripping Length:
8 mm
RoHS Status:
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Ambient Air Temperature:
Operation -40 ... +80 °C
Width in Number of Modular Spacings:
1
Product Net Width:
95 mm
Product Net Height:
87 mm
Product Net Depth / Length:
18 mm
Product Net Weight:
.100 kg
Package Level 1 Units:
1 piece
WEEE Category:
5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B:
Business To Business
CN8:
8536304000