Trade Price
POA
Per
Unit
Pack Quantity
ESP 50H 50V DATA SPD FOR 2 WIRE LINES UP TO 4A CURRENT
Standards:
IEC 61643-21
Suitable For:
To protect systems against transient overvoltages or surges from lightning and electrical switching events
Nominal AC Voltage of the System (Uo):
50 V
Voltage Protection Level ( Up):
65.0 V
Maximum Continuous Operating Voltage (Uc):
56.7 V
Rated Current (In):
4 A
Discharge Current:
I (max, 8 / 20 µs) 10 kA
Rated Frequency (f):
120 kHz
Number of Protected Poles:
1
Connection Type:
Screw Clamp
Serial Resistance:
0.05 Ω
Wire Stripping Length:
6 mm
RoHS Status:
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Ambient Air Temperature:
Operation -40 ... +80 °C
Width in Number of Modular Spacings:
1
Product Net Width:
120 mm
Product Net Height:
54 mm
Product Net Depth / Length:
19 mm
Product Net Weight:
0.080 kg
Package Level 1 Units:
1 piece
WEEE Category:
5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B:
Business To Business
CN8:
8536100040