LUCCX6B

UNIT 0.15-0.6A24VAC

Trade Price

£96.56

Per

1

Unit

EA

Pack Quantity

1

LUCCX6B

Information

TeSys U control and diagnostic unit to be inserted in advanced power bases LUB120, LUB320, LUB380 to form a TeSys U starter controller, for 1-phase motor applications up to 0.04kW@400V. It provides full protection to motors with a rated current Ir 0.15-0.6A (Ir adjustable), overload tripping class 10, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only). For diagnostics, it provides a thermal overload alarm to be managed with an additional function module (to be ordered separately) and a test push button for overload simulation. To be used with a 24V AC voltage for the control of the starter (through the control terminals A1/A2 located in the power base). Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Technical Specifications

Range

TeSys

Range of product

TeSys Ultra

Product name

TeSys Ultra

Device short name

LUCC

Product or component type

Advanced control unit

Device application

Motor control Motor protection

Product specific application

Basic protection and advanced functions, communication

main function available

Protection against overload and short-circuit Manual reset Protection against phase failure and phase imbalance Earth fault protection

Product compatibility

Power base LUB12 Power base LUB32 Power base LUB38 Power base LUB120 Power base LUB320 Power base LUB380 Reversing contactor breaker LU2B12B Reversing contactor breaker LU2B32B

[Ue] rated operational voltage

690 V AC

Network frequency

40...60 Hz

Load type

Single-phase motor

utilisation category

AC-43 AC-44 AC-41

rated motor current adjustment range

0.15…0.6 A

Thermal overload class

Class 10 - frequency limit: 40…60 Hz - temperature compensation: -25…55 °C conforming to IEC 60947-6-2 Class 10 - frequency limit: 40…60 Hz - temperature compensation: -25…55 °C conforming to UL 508

Tripping threshold

14.2 x Ir +/- 20 %

[Uc] control circuit voltage

24 V AC

Control circuit voltage limits

20...26.5 V for AC circuit 24 V in operation 14.5 V for AC circuit 24 V drop-out

Typical current consumption

140 mA at 24 V AC I maximum while closing with LUB12 220 mA at 24 V AC I maximum while closing with LUB32 220 mA at 24 V AC I maximum while closing with LUB38 70 mA at 24 V AC I rms sealed with LUB12 90 mA at 24 V AC I rms sealed with LUB32 90 mA at 24 V AC I rms sealed with LUB38

Heat dissipation

2 W for control circuit with LUB12 3 W for control circuit with LUB32 3 W for control circuit with LUB38

Operating time

35 ms opening with LUB12 for control circuit 35 ms opening with LUB32 for control circuit 35 ms opening with LUB38 for control circuit 70 ms closing with LUB12 for control circuit 70 ms closing with LUB32 for control circuit 70 ms closing with LUB38 for control circuit

Reset

Manual reset

Standards

EN 60947-6-2 IEC 60947-6-2 UL 60947-4-1, with phase barrier CSA C22.2 No 60947-4-1, with phase barrier

product certifications

CE UL CSA CCC EAC ASEFA ATEX Marine

[Ui] rated insulation voltage

690 V conforming to IEC 60947-6-2 600 V conforming to UL 60947-4-1 600 V conforming to CSA C22.2 No 60947-4-1

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-6-2

Safe separation of circuit

400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1 400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1

Fixing mode

Plug-in (front face)

Width

45 mm

height

66 mm

Depth

60 mm

Compatibility code

LUCC

IP degree of protection

IP20 front panel and wired terminals conforming to IEC 60947-1 IP20 other faces conforming to IEC 60947-1 IP40 front panel outside connection zone conforming to IEC 60947-1

Protective treatment

TH conforming to IEC 60068

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-40…85 °C

Operating altitude

2000 m

Fire resistance

960 °C parts supporting live components conforming to IEC 60695-2-12 650 °C conforming to IEC 60695-2-12

Shock resistance

10 gn power poles open conforming to IEC 60068-2-27 15 gn power poles closed conforming to IEC 60068-2-27

Vibration resistance

2 gn, 5…300 Hz, power poles open conforming to IEC 60068-2-6 4 gn, 5…300 Hz, power poles closed conforming to IEC 60068-2-6

Resistance to electrostatic discharge

8 kV level 3 in open air conforming to IEC 61000-4-2 8 kV level 4 on contact conforming to IEC 61000-4-2

Non-dissipating shock wave

1 kV serial mode conforming to IEC 60947-6-2 2 kV common mode conforming to IEC 60947-6-2

Resistance to radiated fields

10 V/m 3 conforming to IEC 61000-4-3

Resistance to fast transients

2 kV class 3 serial link conforming to IEC 61000-4-4 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4

Immunity to radioelectric fields

10 V conforming to IEC 61000-4-6

Immunity to microbreaks

3 ms

Immunity to voltage dips

70 % / 500 ms conforming to IEC 61000-4-11

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

5.5 cm

Package 1 Width

8.5 cm

Package 1 Length

10.2 cm

Package 1 Weight

124.0 g

Unit Type of Package 2

S02

Number of Units in Package 2

23

Package 2 Height

15.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

3.383 kg

Warranty

18 months

Document Links

Datasheet