CA2KN40U7

Control relay 4NO contacts

Trade Price

£33.78

Per

1

Unit

EA

Pack Quantity

1

CA2KN40U7

Information

TeSys K control relay, 4 contacts (4NO), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 230-240V 50/60Hz AC control circuit, connection by screw clamp terminals. For high operating rates until 180 cycles/min and ambient temperature -25/+50°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium product (RoHS/REACh).

Technical Specifications

Range

TeSys

Product name

TeSys CAK

Product or component type

Control relay

Device short name

CA2K

contactor application

Control circuit

utilisation category

DC-13 AC-15

Pole contact composition

4 NO

[Ue] rated operational voltage

<= 690 V <= 400 Hz

Control circuit type

AC at 50/60 Hz

[Uc] control circuit voltage

230...240 V AC 50/60 Hz

[Ith] conventional free air thermal current

10 A (at 50 °C)

Irms rated making capacity

110 A conforming to IEC 60947

Associated fuse rating

10 A gG conforming to IEC 60947 10 A gG conforming to VDE 0660

[Ui] rated insulation voltage

690 V conforming to IEC 60947 750 V conforming to VDE 0110 group C 690 V conforming to BS 5424 600 V conforming to CSA C22.2 No 14

mounting support

Rail Plate

Connections - terminals

Screw clamp terminals 1 cable(s) 1.5…4 mm²solid Screw clamp terminals 2 cable(s) 1.5…4 mm²solid Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible with cable end Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end Screw clamp terminals 1 cable(s) 0.34…1.5 mm²flexible with cable end Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible without cable end

Tightening torque

1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm 1.3 N.m - on screw clamp terminals - with screwdriver Philips No 26 mm 1.3 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

Control circuit voltage limits

Drop-out: 0.2...0.75 Uc (at <50 °C) Operational: 0.8...1.15 Uc (at <50 °C)

Operating time

10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing

Mechanical durability

10 Mcycles

Maximum operating rate

10000 cyc/h

Immunity to microbreaks

2 ms

Inrush power in VA

30 VA (at 20 °C)

Hold-in power consumption in VA

4.5 VA (at 20 °C)

Heat dissipation

1.3 W

Minimum switching voltage

17 V

Minimum switching current

5 mA

Non overlap distance

0.5 mm

Insulation resistance

> 10 MOhm

height

58 mm

Width

45 mm

Depth

57 mm

Net weight

0.18 kg

Standards

EN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1

product certifications

CB Scheme CCC UL CSA EAC CE UKCA

IP degree of protection

IP2X

Protective treatment

TC conforming to IEC 60068

Ambient air temperature for operation

-25…50 °C

Ambient air temperature for storage

-50…80 °C

Operating altitude

2000 m without derating

Flame retardance

V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102

Mechanical robustness

Vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

6.5 cm

Package 1 Width

4.8 cm

Package 1 Length

6.2 cm

Package 1 Weight

180 g

Unit Type of Package 2

S02

Number of Units in Package 2

50

Package 2 Height

15 cm

Package 2 Width

30 cm

Package 2 Length

40 cm

Package 2 Weight

9.338 kg

Warranty

18 months

Document Links

Datasheet

Technical Data