Trade Price
£22,165.62
Per
1
Unit
EA
Pack Quantity
1
Presentation
High density, double-conversion on-line power protection with scalable runtime.
Lead time
Usually in Stock
Main Input Voltage
230 V 400 V 3 phases
Product or component type
Uninterruptible power supply (UPS)
Other Input Voltage
220 V 240 V
Main Output Voltage
230 V
Other Output Voltage
220 V 240 V
Rated power in W
16000 W
Rated power in VA
20000 VA
output connection type
2 IEC Jumpers 8 IEC 60320 C19
Output connector type
Hard wire 3-wire (H N + E) 1 Hard wire 5-wire (3P + N + E) 1
Number of rack unit
12U
Battery type
Lead-acid battery
Provided equipment
CD with software Rack mounting support rails Smart UPS signalling RS-232 cable User manual Web/SNMP management card
Run Time
View Runtime Graph
Efficiency
93 % (in battery operation)
Number of battery filled slots
4
Number of battery free slots
0
Battery recharge time
2.5 h
Number of battery replacement quantity
4
Additional information
Configurable for 400 or 415 V 3 Phase nominal output voltage
Battery voltage
+/- 192 V (split battery referenced to neutral)
Discharge battery voltage
+/- 154 V
Battery charger power
1530 W rated
Battery life
3…5 year(s)
Replacement battery
APCRBC140
Extended runtime
1
UPS type
Double conversion online
Number of power module free slots
0
Number of power module filled slots
0
Redundant
No
Colour
Black
height
53.3 cm
Width
43.2 cm
Depth
77.3 cm
Net weight
247.73 kg
Mounting location
Front
Mounting preference
Lower
Mounting mode
Rack-mounted
Two post mountable
0
USB compatible
No
Network frequency
40...70 Hz auto-sensing
Number of input connectors
1 hard wire 3-wire (1P + N + E) 1 hard wire 5-wire (3P + N + E)
Input voltage limits
160...280 V
Maximum input current
115 A
Switching current capacity
125 A
Input harmonic distortion
Less than 5 % for full load
Input current
115 A (1 phase) 38.3 A per phase (3 phases)
Input Power Factor at Full Load
0.98
Maximum configurable power in VA
20000 VA
Maximum configurable power in W
16000 W
Output frequency
50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Hz sync to mains
Wave type
Sine wave
Output overload operation
60 seconds at 125% and 30 seconds at 150%
Harmonic distortion
Less than 5 %
Crest factor
3 : 1
bypass type
Built-in static bypass Internal bypass (automatic and manual) Optional external bypass
product certifications
BSMI VDE
Standards
EN/IEC 62040-1:2019/A11:2021 EN/IEC 62040-2:2006/AC:2006 EN/IEC 62040-2:2018
Ambient air temperature for operation
0…40 °C
Relative humidity
0…95 % non-condensing
Operating altitude
0...10000 ft
Ambient air temperature for storage
-15…45 °C
Storage Relative Humidity
0…95 % non-condensing
Storage altitude
0.00…15240.00 m
Acoustic level
59 dBA
Heat dissipation
3770 Btu/h
IP degree of protection
IP20
Free slots
0
Preinstalled device
Network management card 2 with environmental monitoring
Emergency power off
Yes
Noise suppression
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
99 cm
Package 1 Width
61 cm
Package 1 Length
100.3 cm
Package 1 Weight
314.09 kg
Unit Type of Package 2
PAL
Number of Units in Package 2
2
Package 2 Height
111 cm
Package 2 Width
100 cm
Package 2 Length
120 cm
Package 2 Weight
626.864 kg
Warranty
2 years repair or replace
Datasheet