Trade Price
£614.16
Per
1
Unit
EA
Pack Quantity
1
Presentation
Intelligent and efficient power protection enabling multi-regional deployment.
Lead time
Usually Ships within 4 Weeks
Main Input Voltage
230 V
Main Output Voltage
230 V
Rated power in W
500 W
Rated power in VA
750 VA
Input Connection Type
IEC 320 C14
output connection type
6 IEC 320 C13 2 IEC Jumpers
Battery type
Lead-acid battery
Provided equipment
CD with software Documentation CD Smart UPS signalling RS-232 cable User manual
Run Time
View Runtime Graph
Efficiency
View Efficiency Graph
Additional information
Configurable for 220 or 230V nominal output voltage
Battery voltage
24 V
Extended runtime
0
Battery capacity
7.0 Ah
Number of battery filled slots
0
Number of battery free slots
0
Battery recharge time
3 h
Number of battery replacement quantity
1
Battery life
3…5 year(s)
Replacement battery
RBC48
Battery power in VAH
149 VAh runtime
Battery charger power
50 W rated
Number of power module filled slots
0
Number of power module free slots
0
Redundant
No
Variant option
Factory set voltage
Colour
Black
height
15.7 cm
Width
13.7 cm
Depth
35.8 cm
Net weight
13.18 kg
Mounting preference
No preference
Mounting mode
Not rack-mountable
Two post mountable
0
USB compatible
No
Input voltage limits
151...302 V adjustable 160...285 V
Network frequency
50/60 Hz +/- 3 Hz auto-sensing
Harmonic distortion
Less than 5 % at full load
Maximum configurable power in VA
750 VA
Maximum configurable power in W
500 W
Transfer time
4 ms typical : 8 ms maximum
UPS type
Line interactive
Wave type
Sine wave
product certifications
CE
Standards
EN/IEC 62040-1:2019/A11:2021 EN/IEC 62040-2:2006/AC:2006 EN/IEC 62040-2:2018
Acoustic level
55 dBA
Heat dissipation
90 Btu/h
Operating altitude
0...10000 ft
Ambient air temperature for operation
0…40 °C
Ambient air temperature for storage
-15…45 °C
Storage altitude
0.00…15240.00 m
Relative humidity
0…95 %
Storage Relative Humidity
0…95 %
control panel
LED status display with load and battery bar-graphs and on line : on battery : replace battery : and overload indicators
Free slots
1
Alarm
Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm
Let through voltage rating
400 V
Surge energy rate
340 J
Noise suppression
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
27.9 cm
Package 1 Width
49.5 cm
Package 1 Length
27.3 cm
Package 1 Weight
14.55 kg
Warranty
2 years repair or replace