LV432097

NO ORDER 3P3D MICROLOGIC 5.3 E 400A TRIP

Trade Price

£1,337.32

Per

1

Unit

EA

Pack Quantity

1

LV432097

Information

This Micrologic 5.3 E (Energy) is a 3 poles 3d electronic trip unit used on Compact NSX 400/630 circuit breakers. This 400A rating electronic trip unit is an optimum choice for all standard and specific applications. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 5.3 E indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. Micrologic 5.3 E is equipped with a display module that gives energy measurement and allows fine adjustment settings. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.

Technical Specifications

Range

ComPact

Range of produc

ComPact NSX400...630

Product or component type

Trip unit

Trip unit name

MicroLogic 5.3 E

Trip unit technology

Electronic

Range compatibility

ComPact NSX400 ComPact NSX630

Device application

Distribution

Number of poles

3P

Protected poles description

3t

Trip unit protection functions

LSI

Protection type

L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection

Trip unit rated current

400 A at 40 °C

[Ue] rated operational voltage

690 V AC 50/60 Hz

Network type

AC

Network frequency

50/60 Hz

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable 9 settings

[Ir] long-time protection pick-up adjustment range

160...400 A

Long-time protection delay adjustment type tr

Adjustable

[tr] long-time protection delay adjustment range

15…400 s at 1.5 x Ir 0.35…11 s at 7.2 x Ir 0.5…16 s at 6 x Ir

thermal memory

20 minutes before and after tripping

Short-time protection pick-up adjustment type Isd

Adjustable 9 settings

[Isd] Short-time protection pick-up adjustment range

1.5...10 x Ir

Short-time protection delay adjustment type tsd

Adjustable

[tsd] Short-time protection delay adjustment range

0…0.4 s I²t=off 0.1…0.4 s I²t=on

Instantaneous protection pick-up adjustment type Ii

Adjustable

[Ii] instantaneous protection pick-up adjustment range

1.5...12 x In

earth-leakage protection

Without

Zone selective interlocking ZSI

With

Local signalling

Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload

Display type

LCD display

Type of measurement

Energy meter

communication of data

Time-stamped histories and event tables Energy metering Protection and alarm settings Power quality Maintenance indicators Instantaneous and demand values Maximeters/minimeters Demand current and power

electrical data recording

Maintenance indicators

Standards

EN/IEC 60947-2 UL 508

product certifications

CCC Marine EAC

ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-40…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

13.800 cm

Package 1 Width

17.500 cm

Package 1 Length

21.600 cm

Package 1 Weight

1.487 kg

Unit Type of Package 2

S04

Number of Units in Package 2

10

Package 2 Height

30.000 cm

Package 2 Width

40.000 cm

Package 2 Length

60.000 cm

Package 2 Weight

15.430 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet