LV431480

250A 4P NSX250 ML 2.2

Trade Price

£696.18

Per

1

Unit

EA

Pack Quantity

1

LV431480

Information

This Micrologic 2.2 is a 4 poles 4d electronic trip unit used on Compact NSX 250 circuit breakers. This 250A rating electronic trip unit is an optimum choice for all standard and specific applications. It embeds an adjustable long time protection against overloads. It provides also an adjustable short-time protection and a fixed instantaneous protection against short-circuits. Micrologic 2.2 indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.

Technical Specifications

Range

ComPact

Range of produc

ComPact NSX100...250

Product or component type

Trip unit

Trip unit name

MicroLogic 2.2

Trip unit technology

Electronic

Range compatibility

ComPact NSX250

Device application

Distribution

Number of poles

4P

Protected poles description

4t 3t + N/2 3t

Neutral position

Left

Trip unit protection functions

LSoI

Protection type

L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection

Trip unit rated current

250 A at 40 °C

[Ue] rated operational voltage

690 V AC 50/60 Hz

Network type

AC

Network frequency

50/60 Hz

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable 9 settings

[Ir] long-time protection pick-up adjustment range

100...250 A

Long-time protection delay adjustment type tr

Fixed

[tr] long-time protection delay adjustment range

11 s at 7.2 x Ir 16 s at 6 x Ir 400 s at 1.5 x Ir

thermal memory

20 minutes before and after tripping

Short-time protection pick-up adjustment type Isd

Adjustable 9 settings

[Isd] Short-time protection pick-up adjustment range

1.5...10 x Ir

Short-time protection delay adjustment type tsd

Fixed

[tsd] Short-time protection delay adjustment range

0.02 s

Instantaneous protection pick-up adjustment type Ii

Fixed

[Ii] instantaneous protection pick-up adjustment range

3000 A

earth-leakage protection

Without

Neutral protection settings

0.5 x Ir (3t + N/2) 1 x Ir (4t) No protection (3t)

Zone selective interlocking ZSI

Without

Local signalling

Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload

Standards

UL 508 EN/IEC 60947-2

product certifications

CCC Marine EAC

ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-50…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

6.5 cm

Package 1 Width

9.2 cm

Package 1 Length

15.0 cm

Package 1 Weight

570.0 g

Unit Type of Package 2

S03

Number of Units in Package 2

23

Package 2 Height

30.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

13.6 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet