Trade Price
£597.89
Per
1
Unit
EA
Pack Quantity
1
This is a 4 poles basic frame for Compact NSX250F. Compact NSX is designed to optimize space and breaking capacity for all standard and specific applications. This basic frame comes without trip unit, and is compatible with any type of trip unit which has to be ordered separately The breaking capacity Icu is 36kA at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz (limited to 440VAC 50/60Hz if there is an earth-leakage protection). It can be equipped with a variety of optional functions and accessories. The dimensions are 140mm x 161mm x 86mm. It ensures compliance with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX250F is part of Schneider Electric EcoStruxure Power architecture.
Range
ComPact
Range of produc
ComPact NSX100...250
Device short name
NSX250F
Product or component type
Basic frame
Device application
Distribution
circuit breaker name
Compact NSX250F
Number of poles
4P
Neutral position
Left
[In] rated current
250 A at 40 °C
[Ue] rated operational voltage
690 V AC 50/60 Hz
Network type
AC
Network frequency
50/60 Hz
Suitability for isolation
Yes conforming to EN/IEC 60947-2
utilisation category
Category A
[Icu] rated ultimate short-circuit breaking capacity
85 kA at 240 V AC 50/60 Hz conforming to UL 508 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 480 V AC 50/60 Hz conforming to UL 508 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 600 V AC 50/60 Hz conforming to UL 508
Performance level
F 36 kA 415 V AC
control type
Toggle
Mounting mode
Fixed
[Ui] rated insulation voltage
800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability
20000 cycles conforming to IEC 60947-2
Electrical durability
10000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 10000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 20000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2 5000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2
mounting support
Backplate
Upside connection
Front
downside connection
Front
Connection pitch
35 mm
Protection type
Without protection
Width (W)
140 mm
Height (H)
161 mm
Depth (D)
86 mm
Standards
EN/IEC 60947-2 UL 508
product certifications
UL CSA
Pollution degree
3 conforming to IEC 60664-1
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to IEC 62262
ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-50…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
13.900 cm
Package 1 Width
14.700 cm
Package 1 Length
19.200 cm
Package 1 Weight
2.119 kg
Unit Type of Package 2
S04
Number of Units in Package 2
11
Package 2 Height
30.000 cm
Package 2 Width
40.000 cm
Package 2 Length
60.000 cm
Package 2 Weight
24.042 kg
Warranty
18 months
Datasheet