LV430496

Information

This Micrologic 5.2 E (Energy) is a 4 poles 4d electronic trip unit used on Compact NSX 160/250 circuit breakers. This 160A rating electronic trip unit is an optimum choice for all standard and specific applications. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 5.2 E indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. Micrologic 5.2 E is equipped with a display module that gives energy measurement and allows fine adjustment settings. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.

Technical Specifications

Range

ComPact

Range of produc

ComPact NSX100...250

Product or component type

Trip unit

Trip unit name

MicroLogic 5.2 E

Trip unit technology

Electronic

Range compatibility

ComPact NSX160 ComPact NSX250

Device application

Distribution

Number of poles

4P

Protected poles description

4t 3t + OSN 3t + N/2 3t

Neutral position

Left

Trip unit protection functions

LSI

Protection type

L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection

Trip unit rated current

160 A at 40 °C

[Ue] rated operational voltage

690 V AC 50/60 Hz

Network type

AC

Network frequency

50/60 Hz

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable 9 settings

[Ir] long-time protection pick-up adjustment range

63...160 A

Long-time protection delay adjustment type tr

Adjustable

[tr] long-time protection delay adjustment range

15…400 s at 1.5 x Ir 0.35…11 s at 7.2 x Ir 0.5…16 s at 6 x Ir

thermal memory

20 minutes before and after tripping

Short-time protection pick-up adjustment type Isd

Adjustable 9 settings

[Isd] Short-time protection pick-up adjustment range

1.5...10 x Ir

Short-time protection delay adjustment type tsd

Adjustable

[tsd] Short-time protection delay adjustment range

0…0.4 s I²t=off 0.1…0.4 s I²t=on

Instantaneous protection pick-up adjustment type Ii

Adjustable

[Ii] instantaneous protection pick-up adjustment range

1.5...15 x In

earth-leakage protection

Without

Neutral protection settings

0.5 x Ir (3t + N/2) 1 x Ir (4t) 1.6 x Ir (3t + OSN) No protection (3t)

Zone selective interlocking ZSI

With

Local signalling

Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload

Display type

LCD display

Type of measurement

Energy meter

communication of data

Instantaneous and demand values Protection and alarm settings Demand current and power Power quality Energy metering Maintenance indicators Maximeters/minimeters Time-stamped histories and event tables

electrical data recording

Maintenance indicators

Standards

UL 508 EN/IEC 60947-2

product certifications

CCC EAC Marine

ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-40…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

9.8 cm

Package 1 Width

11.0 cm

Package 1 Length

15.2 cm

Package 1 Weight

668.0 g

Unit Type of Package 2

S03

Number of Units in Package 2

11

Package 2 Height

30.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

7.835 kg

Warranty

18 months