LV430470

OBSOLETE - O2 - USE C1632D160

Trade Price

£420.96

Per

1

Unit

EA

Pack Quantity

1

LV430470

Information

This Micrologic 2.2 is a 3 poles 3d electronic trip unit used on Compact NSX 160/250 circuit breakers. This 160A rating electronic trip unit is an optimum choice for all standard and specific applications. It embeds an adjustable long time protection against overloads. It provides also an adjustable short-time protection and a fixed instantaneous protection against short-circuits. Micrologic 2.2 indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.

Technical Specifications

Range

ComPact

Range of produc

ComPact NSX100...250

Product or component type

Trip unit

Trip unit name

MicroLogic 2.2

Trip unit technology

Electronic

Range compatibility

ComPact NSX160 ComPact NSX250

Device application

Distribution

Number of poles

3P

Protected poles description

3t

Trip unit protection functions

LSoI

Protection type

L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection

Trip unit rated current

160 A at 40 °C

[Ue] rated operational voltage

690 V AC 50/60 Hz

Network type

AC

Network frequency

50/60 Hz

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable 9 settings

[Ir] long-time protection pick-up adjustment range

63...160 A

Long-time protection delay adjustment type tr

Fixed

[tr] long-time protection delay adjustment range

11 s at 7.2 x Ir 16 s at 6 x Ir 400 s at 1.5 x Ir

thermal memory

20 minutes before and after tripping

Short-time protection pick-up adjustment type Isd

Adjustable 9 settings

[Isd] Short-time protection pick-up adjustment range

1.5...10 x Ir

Short-time protection delay adjustment type tsd

Fixed

[tsd] Short-time protection delay adjustment range

0.02 s

Instantaneous protection pick-up adjustment type Ii

Fixed

[Ii] instantaneous protection pick-up adjustment range

2400 A

earth-leakage protection

Without

Zone selective interlocking ZSI

Without

Local signalling

Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload

Standards

UL 508 EN/IEC 60947-2

product certifications

Marine EAC CCC

ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-50…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

6.5 cm

Package 1 Width

9.5 cm

Package 1 Length

11 cm

Package 1 Weight

440 g

Unit Type of Package 2

S03

Number of Units in Package 2

28

Package 2 Height

30 cm

Package 2 Width

30 cm

Package 2 Length

40 cm

Package 2 Weight

12.66 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet