Trade Price
£14,630.24
Per
1
Unit
EA
Pack Quantity
1
Presentation
Highly efficient, easy-to-deploy 20kW, 400V 3-phase uninterruptible power supply (UPS) that brings best-in-class power protection to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Compact design, high-density technology and modular architecture keep total cost of ownership low and operational efficiency at the highest levels. Galaxy VS reduces your energy losses by up to 66% with the patented ECOnversion mode – reaching up to 99% efficiency levels and delivering more energy savings than even our industry-leading 97% efficiency in normal operating mode. The UPS is EcoStruxure-ready to give you peace of mind with cloud-based remote monitoring and management via your smartphone. Includes 5x8 start-up service. For battery runtime details, see the runtime charts published under the Documents tab.
Lead time
Usually Ships within 2 Weeks
Main Input Voltage
400 V 3 phases
Other Input Voltage
380 V 415 V
Main Output Voltage
400 V 3 phases
Other Output Voltage
380 V 415 V
Rated power in W
20 kW
Rated power in VA
20 kVA
Output connector type
Hard wire 5-wire (3P + N + E) 1
Battery type
External battery system Li-Ion (Lithium-Ion) VRLA
Provided equipment
Dust filter Installation guide Integrated network management Power modules ship installed Start-up service Top and bottom cable entry
Efficiency
View Efficiency Graph
Number of battery filled slots
0
Number of battery free slots
0
Battery voltage
384...576 V DC
Discharge battery voltage
307 V DC
Max current discharge
68 A
Battery power in VAH
0 VAh runtime
Extended runtime
0
Bypass voltage tolerance
+/- 10 %
Max bypass input current
32 A
Redundant
No
Colour
White
height
148.5 cm
Width
52.1 cm
Depth
84.7 cm
Net weight
206 kg
USB compatible
No
Network frequency
40...70 Hz
Number of input connectors
1 hard wire 4-wire (3P + E) 1 hard wire 5-wire (3P + N + E)
Input voltage limits
340...460 V 400 V
Maximum input current
37 A
Max short time withstand current
65 kA
Input harmonic distortion
Less than 3 % for full load
Load power factor
From 0.7 leading to 0.7 lagging without any derating
Input Power Factor at Full Load
0.99
Maximum configurable power in W
20 kW
Harmonic distortion
Less than 3 %
Output frequency
50 Hz sync to mains 60 Hz sync to mains 60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
Crest factor
2.5
Wave type
Sine wave
Output voltage tolerance
+/-1% after 50ms
Output harmonic distortion
< 1% linear load and < 3% non-linear load
Output overload operation
10 minutes at 125% and 60 seconds at 150%
bypass type
Built-in static bypass
Maximum configurable power in VA
20 kVA
standards
CSA C22.2 No 107.3 EN/IEC 62040-1 EN/IEC 62040-2 EN/IEC 62040-3 FCC part 15 class A IEC 60721-4-2 level 2M2 UL 1778 5th edition
Ambient air temperature for operation
0…40 °C
Relative humidity
0…95 % non-condensing
Operating altitude
0...3281 ft
Ambient air temperature for storage
-25…55 °C
Storage Relative Humidity
10…80 % non-condensing
Storage altitude
0.00…15240.00 m
Acoustic level
65 dBA
Heat dissipation
2187.8 Btu/h
IP degree of protection
IP21
Free slots
1
control panel
Touch screen LCD user interface
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
168 cm
Package 1 Width
99 cm
Package 1 Length
64 cm
Package 1 Weight
235 kg
Warranty
1 year on-site repair or replace with factory authorized Start-Up
Datasheet