Trade Price
£84,185.36
Per
1
Unit
EA
Pack Quantity
1
The PowerLogic DVR series offer to industry a solution to regulate voltage and restore Sags. This equipment is part of the Dynamic Voltage Restorer solution, and do not work stand alone. The secondary unit brings additional capacity to the system power. Protection of sensitive loads in power distribution and transmission systems against voltage distortions. This secondary equipement combined with the main apparatus contribute to the -40 % sags correction at 400 VAC, for a system power of 600 kVA. Enclosure dimensions are 2152 mm in height, 1214 mm in width and 750 mm in depth, and a total weight of 1250 kg. The device passed the following tests: SEMI F47 (US) / IEC 61000-4-34 for sags performances, and received CE, Ctick and EAC certifications. The enclosures is floor standing, equiped with hinged doors locked by a special opening tool. Include a forced ventillation to cool the inverter and the transformer. The design of the equipement allows connection to Source and Loads from the top or bottom, but to DVR input and output only from the bottom. This asset is compatible with EcoStruxure Power Advisor and EcoStruxure Asset Advisor, and could be supported by a service plan. The PowerLogic DVR is designed to reduce voltage sags on power lines that cater to sensitive commercial and industrial equipments.
Product or component type
Voltage module
Network type
3P 3P + N
Network rated voltage
400 V AC
Network frequency
50/60 Hz +/- 10 %
[THDU] total harmonic distorsion
0…5 % (nominal) 5…8 % (maximum): output voltage regulated at +/- 1 % 8…10 % (short time): output voltage regulated at +/- 3 % 10 % (limit)
Sag correction capability
For 3 phases 40 % for 30 s, accuracy +/- 1 %
Sag correction response
3 ms
Ride-through time
40 ms
Output voltage accuracy
+/- 1 % typical
Admitted output load
Up to 100% in variation Up to 100% in unbalance Inverter overload 110 %, 30 s Inverter overload 150 %, 1 s
Efficiency
at global efficiency load factor (98 %) Linear load at at nominal power load factor ,PF 0.8 (97.7 %) Linear load at at nominal power load factor ,PF 1 (98.1 %) Non-linear load at at nominal power load factor (97.4 %)
Continuous regulation range
-20…20 %
Power capacity
600 kVA
Overload withstand
2 In, 60 s 5 In, 10 s 30 In, 200 ms 30 In, if overload is exceeded equipment integrity is not guaranteed, 200 ms
Mean time to repair
2 h
enclosure mounting
Floor-standing
Heat dissipation
Secondary function
Electromagnetic compatibility
Voltage dips and interruptions immunity test conforming to IEC 61000-4-34 Immunity for industrial environments conforming to IEC 61000-6-2 Emission standard for industrial environments conforming to IEC 61000-6-4
accessibility for operation
Front
Location of connection
Bottom
Type of cooling
Forced cooling
Noise level
75 dB
Material
Cold-rolled steel Hot-rolled steel
Surface finish
Polyester powder
Enclosure degree of protection
IP20
Overvoltage category
III
Pollution degree
2
Operating altitude
<= 1000 m without derating
Ambient air temperature for operation
0…40 °C
Relative humidity
0…95 % non-condensing
Standards
IEC 62477-1 SEMI F47 ISO 14001 ISO 9001
product certifications
CE EAC C-Tick
Ambient air temperature for storage
-15…45 °C
Net weight
1250 kg
height
2152 mm
Width
1214 mm
Colour
Light grey (RAL 7035)
Depth
750 mm
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
236.0 cm
Package 1 Width
84.5 cm
Package 1 Length
132.0 cm
Package 1 Weight
1425.0 kg
Warranty
18 months
Datasheet