Trade Price
POA
Per
1
Unit
EA
Pack Quantity
1
Range of produc
Altivar Process ATV900
Device application
Industrial application
Product or component type
Variable speed drive
Product destination
Synchronous motors Asynchronous motors
Product specific application
Process for industrial
variant
Standard version With braking chopper
Network number of phases
3 phases
Mounting mode
Wall mount
communication port protocol
EtherNet/IP Modbus serial Modbus TCP
[Us] rated supply voltage
600 V - 15...10 %
Continuous output current
27 A at 4 kHz for normal duty 22 A at 4 kHz for heavy duty
EMC filter
Integrated With EMC plate option
IP degree of protection
IP20
Degree of protection
UL type 1
option module
Slot A: communication module for Profibus DP V1 Slot A: communication module for PROFINET Slot A: communication module for DeviceNet Slot A: communication module for EtherCAT Slot A: communication module for CANopen daisy chain RJ45 Slot A: communication module for CANopen SUB-D 9 Slot A: communication module for CANopen screw terminals Slot A/slot B/slot C: digital and analog I/O extension module Slot A/slot B/slot C: output relay extension module Slot B: 5/12 V digital encoder interface module Slot B: analog encoder interface module Slot B: resolver encoder interface module communication module for Ethernet Powerlink
Discrete input logic
Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1) Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1) Positive logic (source) (DI7, DI8), < 0.6 V (state 0), > 2.5 V (state 1) Positive logic (source) (STOA, STOB), < 5 V (state 0), > 11 V (state 1)
Asynchronous motor control profile
Constant torque standard Variable torque standard Optimized torque mode
Synchronous motor control profile
Permanent magnet motor Synchronous reluctance motor
maximum output frequency
599 Hz
Switching frequency
2...8 kHz adjustable 4...8 kHz with derating factor
Nominal switching frequency
4 kHz
Apparent power
24.1 kVA at 600 V (normal duty) 20.4 kVA at 600 V (heavy duty)
Maximum transient current
32.4 A during 60 s (normal duty) 33 A during 60 s (heavy duty)
Network frequency
50...60 Hz
Prospective line Isc
70 kA
Discrete input number
10
Discrete input type
DI1...DI8 programmable, 24 V DC (<= 30 V), impedance: 3.5 kOhm DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V) STOA, STOB safe torque off, 24 V DC (<= 30 V), impedance: > 2.2 kOhm
Discrete output number
2
Discrete output type
Logic output DQ+ 0…1 kHz <= 30 V DC 100 mA Programmable as pulse output DQ+ 0…30 kHz <= 30 V DC 20 mA Logic output DQ- 0…1 kHz <= 30 V DC 100 mA
analogue input number
3
Analogue input type
AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0...20 mA/4...20 mA, impedance: 250 Ohm, resolution 12 bits
analogue output number
2
Analogue output type
Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits Software-configurable current AQ1, AQ2: 0...20 mA impedance 500 Ohm, resolution 10 bits
Relay output number
3
Relay output type
Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles Configurable relay logic R2: sequence relay NO electrical durability 1000000 cycles Configurable relay logic R3: sequence relay NO electrical durability 1000000 cycles
Maximum switching current
Relay output R1 on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC Relay output R2, R3 on resistive load, cos phi = 1: 5 A at 250 V AC Relay output R2, R3 on resistive load, cos phi = 1: 5 A at 30 V DC Relay output R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Minimum switching current
Relay output R1, R2, R3: 5 mA at 24 V DC
Physical interface
Ethernet 2-wire RS 485
Connector type
2 RJ45 1 RJ45
Method of access
Slave Modbus TCP
Transmission rate
10/100 Mbit/s for Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
Transmission frame
RTU
Number of addresses
1…247 for Modbus serial
Data format
8 bits, configurable odd, even or no parity for Modbus serial
Type of polarization
No impedance for Modbus serial
4 quadrant operation possible
True
Acceleration and deceleration ramps
S, U or customized Linear adjustable separately from 0.01...9999 s
Motor slip compensation
Not available in permanent magnet motor law Adjustable Can be suppressed Automatic whatever the load
Braking to standstill
By DC injection
Brake chopper integrated
True
Maximum input current
23.2 A
Maximum output voltage
600.0 V
Relative symmetric network frequency tolerance
5 %
Base load current at high overload
22.0 A
Base load current at low overload
27.0 A
Power dissipation in W
Forced convection: 377 W at 600 V, switching frequency 4 kHz Natural convection: 125 W at 600 V, switching frequency 4 kHz
With safety function Safely Limited Speed (SLS)
True
With safety function Safe brake management (SBC/SBT)
True
With safety function Safe Operating Stop (SOS)
False
With safety function Safe Position (SP)
False
With safety function Safe programmable logic
False
With safety function Safe Speed Monitor (SSM)
False
With safety function Safe Stop 1 (SS1)
True
With sft fct Safe Stop 2 (SS2)
False
With safety function Safe torque off (STO)
True
With safety function Safely Limited Position (SLP)
False
With safety function Safe Direction (SDI)
False
Protection type
Thermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
Quantity per set
1
Width
246 mm
height
567 mm
Depth
242 mm
Net weight
23 kg
Electrical connection
Control: screw terminal 0.5...1.5 mm²/AWG 20...AWG 16 Motor: screw terminal 10 mm²/AWG 8 Line side: screw terminal 10 mm²/AWG 8 DC bus: screw terminal 10 mm²/AWG 8
Exchange mode
Half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
Supply
External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection
Local signalling
Local diagnostic: 3 LED (mono/dual colour) Presence of voltage: 1 LED (red) Embedded communication status: 3 LED (dual colour) Communication module status: 4 LED (dual colour)
Input compatibility
DI1...DI8: discrete input level 1 PLC conforming to IEC 61131-2 DI7, DI8: pulse input level 1 PLC conforming to IEC 65A-68 STOA, STOB: discrete input level 1 PLC conforming to IEC 61131-2
Sampling duration
2 ms +/- 0.5 ms (DI1...DI8) - discrete input 5 ms +/- 1 ms (DI7, DI8) - pulse input 1 ms +/- 1 ms (AI1, AI2, AI3) - analog input 5 ms +/- 1 ms (AQ1, AQ2) - analog output
Accuracy
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
Linearity error
AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AQ1, AQ2: +/- 0.2 % for analog output
Refresh time
Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
Isolation
Between power and control terminals
Operating altitude
<= 1000 m without derating 1000...4800 m with current derating 1 % per 100 m
Operating position
Vertical +/- 10 degree
product certifications
TÜV UL CSA
Marking
CE
Standards
UL 508C IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
Assembly style
Enclosed
Electromagnetic compatibility
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Environmental class (during operation)
Class 3C3 according to IEC 60721-3-3 Class 3S3 according to IEC 60721-3-3
Maximum acceleration under shock impact (during operation)
150 m/s² at 11 ms
Maximum acceleration under vibrational stress (during operation)
10 m/s² at 13...200 Hz
Maximum deflection under vibratory load (during operation)
1.5 mm at 2...13 Hz
Permitted relative humidity (during operation)
Class 3K5 according to EN 60721-3
Volume of cooling air
330 m3/h
Overvoltage category
III
Regulation loop
Adjustable PID regulator
Insulation resistance
> 1 MOhm 500 V DC for 1 minute to earth
Noise level
58 dB
Vibration resistance
1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
Environmental characteristic
Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to IEC 60721-3-3
Relative humidity
5…95 % without condensation conforming to IEC 60068-2-3
Ambient air temperature for operation
-15…50 °C (without derating) 50…60 °C (with derating factor)
Pollution degree
2
Ambient air transport temperature
-40…70 °C
Ambient air temperature for storage
-40…70 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
24.2 cm
Package 1 Width
24.6 cm
Package 1 Length
56.7 cm
Package 1 Weight
23.0 kg
Warranty
18 months
Datasheet