Trade Price
£409.50
Per
1
Unit
EA
Pack Quantity
1
Range of product
Modicon Power Supply
Product or component type
Power supply
Power supply type
Regulated switch mode
Variant option
Universal
Enclosure material
Metal
Nominal input voltage
380...500 V AC three phase
Rated power in W
480 W
Output voltage
48 V DC
Power supply output current
10 A
Permissible temporary current boost
1.5 x In (for 5 seconds)
Input voltage limits
320...575 V AC 3 phases
Nominal network frequency
50…60 Hz
Network system compatibility
TN TT IT
Maximum leakage current
2 mA 500 V AC
Input protection type
Integrated fuse (not interchangeable) 3.15 A External protection (recommended)
Inrush current
35 A at 380 V 35 A at 500 V
Power factor
0.90 at 380 V AC 0.88 at 500 V AC
Efficiency
92 % at 380 V AC 92 % at 500 V AC
Output voltage adjustment
48…56 V
Power dissipation in W
33 W
Current consumption
< 0.85 A 380 V AC < 0.73 A 500 V AC
Turn-on time
< 1 s
Holding time
> 20 ms 380 V AC > 20 ms 500 V AC
Startup with capacitive loads
200000 µF
Residual ripple
< 150 mV
Meantime between failure [MTBF]
890200 h at 25 °C, full load conforming to SR 332 346200 h at 55 °C, 80 % load conforming to SR 332
Output protection type
Against overload and short-circuits, protection technology: manual or automatic reset by switch Against over temperature, protection technology: automatic reset Against overvoltage, protection technology: manual reset
Connections - terminals
Screw connection: 4...6 mm², (AWG 12...AWG 10) without wire end ferrule for output Screw connection: 4 mm², (AWG 12) with wire end ferrule for output Screw connection: 0.75…6 mm², (AWG 18...AWG 10) without wire end ferrule for input Screw connection: 0.75...4 mm², (AWG 18...AWG 12) with wire end ferrule for input Cage clamp: 0.2...1.5 mm², (AWG 22...AWG 16) without wire end ferrule for diagnostic relay Cage clamp: 0.2...0.75 mm², (AWG 22...AWG 18) with wire end ferrule for diagnostic relay Cage clamp: 0.2...0.75 mm², (AWG 22...AWG 18) with wire end ferrule for shut down input
Line and load regulation
< 0.17 % at 100 % load in line at 25 °C < 0.6 % +/- 0.5 % at 150 % load at 25 °C
Status LED
1 LED (green and red) product status
Depth
127.2 mm
height
124 mm
Width
65 mm
Net weight
1.15 kg
Output coupling
Parallel
Marking
CE UKCA
Mounting support
Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 Double-profile DIN rail
Supply
SELV conforming to EN/IEC 60950-1 SELV conforming to EN/IEC 60204-1 SELV conforming to IEC 60364-4-41
Dielectric strength
4000 V AC with input to output 2000 V AC with input to ground 1500 V AC with output to ground 4000 V AC with input to diagnostic relay 500 V AC with output to diagnostic relay 1500 V AC with diagnostic relay to ground with shutdown input not isolated from output
Diagnostic relay
Electromechanical relay 1000.0 mA 30 V
Service life
10 year(s) 40 °C 80 % load
Overvoltage category
III II
standards
EN 62368-1 EN/IEC 61204-3 EN 61000-6-1 EN 61000-6-2 EN 61000-6-3 EN 61000-6-4 EN 61000-3-2 EN 61000-3-3 UL 62368-1 CSA C22.2 No 62368-1 CSA C22.2 No 107.1 EN/IEC 62368-1
Product certifications
CE CUL listed CUL recognized RCM CB Scheme EAC KC UKCA CURus
Operating altitude
< 5000 m overvoltage category III overvoltage category II
Shock resistance
150 m/s² for 11 ms
IP degree of protection
IP20
Ambient air temperature for operation
-25…55 °C without current derating mounting position A < 2000 m 55…70 °C with current derating of 3.3 % per °C mounting position A < 2000 m
Electrical shock protection class
Class I
Pollution degree
2
Vibration resistance
3.5 mm (f= 3…11.9 Hz) conforming to IEC 60068-2-6 20 m/s² (f= 11.9…150 Hz) conforming to IEC 60068-2-6
Electromagnetic immunity
Immunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to EN/IEC 61000-4-2 Immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to EN/IEC 61000-4-2 Immunity to conducted RF disturbances - test level: 15 V/m (80 MHz...2 GHz) conforming to EN/IEC 61000-4-3 Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to EN/IEC 61000-4-3 Immunity to conducted RF disturbances - test level: 5 V/m (2.7...6 GHz) conforming to EN/IEC 61000-4-3 Immunity to fast transients - test level: 4 kV (on input-output) conforming to EN/IEC 61000-4-4 Surge immunity test - test level: 4 kV (between power supply and earth) conforming to EN/IEC 61000-4-5 Surge immunity test - test level: 3 kV (between phases) conforming to EN/IEC 61000-4-5 Immunity to conducted RF disturbances - test level: 15 V (0.15...80 MHz) conforming to EN/IEC 61000-4-6 Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to EN/IEC 61000-4-8 Immunity to voltage dips conforming to EN/IEC 61000-4-11 Disturbing field emission conforming to EN 55016-2-3 Limits for harmonic current emissions conforming to EN 61000-3-2 conforming to EN 55016-1-2 conforming to EN 55016-2-1
Electromagnetic emission
Conducted emissions conforming to EN 61000-6-3 Radiated emissions conforming to EN 61000-6-4
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
9.45 cm
Package 1 Width
17.7 cm
Package 1 Length
18.7 cm
Package 1 Weight
1.512 kg
Unit Type of Package 2
S03
Number of Units in Package 2
7
Package 2 Height
30.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
11.2 kg
Warranty
18 months